Turning the Power ON Section 6-1<br />

6-1-1 Power-up Checklist<br />

After turning the power ON, use the following checklist to verify the Compo-<br />

Bus/S communications have started properly.<br />

Unit Check Answer<br />

Master Are the RUN, SD, and RD indicators lit? Yes No<br />

With CS-series, C200HX/C200HG/C200HE-(Z)E, and C200HS<br />

Master Units, is the ERC indicator OFF?<br />

Yes No<br />

With CS-series Master Units, are the ERH and ERC indicators<br />

OFF?<br />

Yes No<br />

With CJ-series Master Units, are the ERH and ERC indicators<br />

OFF?<br />

Yes No<br />

With a CS-series, C200HX/C200HG/C200HE-(Z)E, and C200HS<br />

Master Unit, CS-series Master Unit, or CJ-series Master Unit,<br />

are the Active Node Flags ON for all of the Slaves connected to<br />

the system?<br />

Yes No<br />

With CQM1 Masters, are the ERS and ERC indicators OFF? Yes No<br />

Slave Are the PWR and COMM indicators lit? Yes No<br />

Is the ERR indicator OFF? Yes No<br />

Is the U.ERR indicator OFF?<br />

(For SRT2-AD04 and SRT2-DA02 Analog Terminals only)<br />

Yes No<br />

Note 1. If any questions are answered “No,” refer to 6-2 Checking Operations for<br />

CS-series, C200HX/C200HG/C200HE-(Z)E, and C200HS Master Units to<br />

6-5 Checking Slave Operations for instructions on identifying and clearing<br />

the cause of the error.<br />

2. For SRM1 and CPM2C-S Master Units, refer to the SRM1 Operation Manual<br />

and CPM2C-S Operation Manual.<br />