Checking Operations of CS-series and CJ-series Master Units Section 6-3<br />

Input Slave Communications Error Flags<br />

These flags indicate whether a communications error has occurred with the<br />

corresponding Input Slaves.<br />

Note 1. Input from Input Slaves and output to Output Slaves is enabled when the<br />

<strong>CompoBus</strong>/S System is started up and the Active Node Flag corresponding<br />

to the Slave is turned ON. During actual operation, it is recommended<br />

to create a ladder program that processes Slave I/O after checking that Active<br />

Node Flags are turned ON and Communications Error Flags are OFF.<br />

2. When a CS-series or CJ-series Master Unit is set to communications stop<br />

mode, communications will stop when the Output Slave Communications<br />

Error Flag or Input Slave Communications Error Flag turns ON.<br />

6-3-3 Checking Status Using Special I/O Unit DM Area<br />

Master Unit’s DM Area<br />

Words and Configuration<br />

Flag status Meaning<br />

0 (OFF) Normal communications or the Slave is not participating in communications.<br />

1 (ON) Withdrawn from communications (communications error)<br />

(This flag turns OFF automatically when the Slave rejoins communications.)<br />

A CS-series and CJ-series Master Unit is allocated an area in the PLC's Special<br />

I/O Unit DM Area for setting and information storage for the Slave registration<br />

function and communications stop mode. Use a Programming Device<br />

(such as the CX-Programmer) to read the area and check the communications<br />

status and which Slave the error occurred in.<br />

The following table shows the location and configuration of the Special I/O<br />

Unit DM Area words used by a CS-series and CJ-series Master Unit.<br />

PLC Location of Status Area<br />

CS-series and CJseries<br />

PLCs<br />

First word = D20000 + unit number × 100<br />

367