03.08.2013 Views

OPERATION MANUAL CompoBus/S

OPERATION MANUAL CompoBus/S

OPERATION MANUAL CompoBus/S

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

I/O Link Units for CPM2C Section 5-10<br />

Terminal Arrangement and Wiring<br />

Note 1. All 8 input and 8 output points use the same node number.<br />

2. The actual node number setting range depends on the PLC model in which<br />

the Master is mounted as well as the Master’s settings. Refer to 2-1 Communications<br />

Specifications for details.<br />

Communications Mode Settings<br />

The following communications modes are set with pin 5 of the DIP switch.<br />

Pin 5<br />

(DR)<br />

Communications<br />

mode<br />

OFF High-speed Communications<br />

Mode<br />

ON Long-distance<br />

Communications<br />

Mode<br />

Communications<br />

distance<br />

Communications<br />

baud rate<br />

Communications<br />

cycle time<br />

100 m max. 750 kbps 0.5 or 0.8 ms<br />

500 m max. 93.75 kbps 4.0 or 6.0 ms<br />

Note 1. Only the C200HW-SRM21-V1, CQM1-SRM21-V1, SRM1-CO@-V2, and<br />

CPM2C-S Master Units can be Long-distance Communications Mode.<br />

2. Make sure that the communications mode of the Slave is the same as that<br />

of the Master Unit. If the communications modes are not the same, normal<br />

communications with the Master Unit will not be possible. The operating<br />

status of the Slave can be verified with LED indicators. Refer to 6-5-1 Indicators<br />

for details.<br />

Hold/Clear Outputs for Communications Error<br />

Pin 6 is used to set the output data status when a communications error<br />

occurs, as shown in the following table.<br />

Pin 6 (HOLD) Setting<br />

OFF Clear output status<br />

ON Maintain output status<br />

<strong>CompoBus</strong>/S<br />

communications<br />

<strong>CompoBus</strong>/S<br />

communications<br />

The BD H terminals are all<br />

connected internally, as<br />

are the BD L terminals.<br />

When viewed from the CPM2C CPU Unit, the 8 input and 8 output points<br />

under the <strong>CompoBus</strong>/S I/O Link Unit are allocated to the I/O memory (input<br />

and output bits) of the CPU Unit, as is the case with Expansion I/O Units. One<br />

input and one output words are allocated. Actual I/O operations are not performed<br />

for the I/O memory of the CPM2C CPU Unit, but it is performed for the<br />

333