CJ1W-SRM21 Master Unit for CJ-series PLCs Section 4-3<br />

Word Bit Name Function<br />

+4 00 Registration Completed<br />

Flag<br />

00 to 07 Reserved for system<br />

use.<br />

08 Verification Error<br />

Flag: Slave Missing<br />

09 Verification Error<br />

Flag: Unregistered<br />

Slave in Network<br />

10 Communications<br />

Stopped Flag<br />

This flag is turned ON when all registered Slaves have joined the network. If<br />

all the registered Slaves have joined the network within the registered Slave<br />

participation monitoring time this flag will turn ON even if unregistered Slaves<br />

have also joined. The flag will not turn ON, however, if there are no Slaves<br />

set in the Slave registration table. The flag will remain ON until the power is<br />

turned OFF and ON again or the Unit is restarted.<br />

This flag is turned ON under the following conditions.<br />

Registered Slaves do not join the network within the registered Slave participation<br />

monitoring time. When the Slave that caused the verification error is<br />

joined in the network, the flag will automatically be turned OFF.<br />

Check which Slave caused the error in the bit for verification error (Slave<br />

missing) in Output Slave (first word + 6) or verification error (Slave missing)<br />

in Input Slave (first word + 7).<br />

This flag is turned ON when an unregistered Slave has joined the network.<br />

The flag will remain ON until the power is turned OFF and ON again or the<br />

Unit is restarted, even if the Slave that caused the verification error is<br />

removed from the network.<br />

Check which Slave caused the error in the bit for Output Slave verification<br />

error (unregistered Slave in network) (first word + 8) or Input Slave verification<br />

error (unregistered Slave in network) (first word + 9).<br />

This flag is turned ON when the Master Unit is set to communications stop<br />

mode and remote I/O communications stop due to a communications error,.<br />

Once the flag has turned ON, the status remains until the power is turned<br />

OFF and ON again or the Unit is restarted.<br />

Check which Slave caused the error in the bits for communications stopped<br />

node number (bits 00 to 07 of first word + 5) and communications stopped<br />

Slave type (bit 15 of first word + 5).<br />

11 to 14 Reserved for system<br />

use.<br />

15 Error Flag This flag is turned ON when any of the bits 08 to 10 are set to1(ON).<br />

The flag is automatically turned OFF when all the bits 08 to 10 are turned<br />

OFF.<br />

+5 00 to 07 Communications<br />

Stopped Node Number<br />

08 to 14 Reserved for system<br />

use.<br />

15 Communications<br />

Stopped Slave type<br />

When the Master Unit is set to communications stop mode and remote I/O<br />

communications stop due to a communications error, the node number of the<br />

Slave that caused the error is stored as a 2-digit hexadecimal (00 to 0F: 1 to<br />

15).<br />

Check the Slave type (Output or Input) in the word for communications<br />

stopped Slave type (bit 15 of first word + 5).<br />

The node address stored will be held until the power is turned OFF and ON<br />

again or the Unit is restarted.<br />

When the Master Unit is set to communications stop mode and remote I/O<br />

communications stop due to a communications error, the Slave type of the<br />

Slave that caused the error is stored as follows:<br />

0 (OFF): Output Slave<br />

1 (ON): Input Slave<br />

Check which Slave caused the error in the bits for communications stopped<br />

node number (bits 00 to 07 of first word + 5)<br />

When communications have stopped, the bit status is held until the power is<br />

turned OFF and ON again or the Unit is restarted.<br />