Remote Terminals Section 5-1<br />

Slave Components The following diagram shows the main components of the SRT@-MD16T (-@)<br />

Remote Terminal. The functions of these components are described below.<br />

Circuit Block Mounting<br />

Screw<br />

Used to remove the circuit block<br />

when replacing it.<br />

Rotary Switch<br />

Sets node number.<br />

DIP Switch<br />

The DIP switch's pins have the following functions:<br />

Pins 1 and 2: Reserved (Always OFF)<br />

Pin 3: Communications mode setting (SRT2 Series)<br />

or Reserved (Always OFF) (SRT1 Series)<br />

Pin 4: Hold/Clear outputs for communications error<br />

<strong>CompoBus</strong>/S Indicators<br />

Indicate the status of the Slave<br />

and communications.<br />

Mounting Screw Holes<br />

Used when screwing the<br />

Unit to a control panel.<br />

DIN Track Mounting Hooks<br />

Used when mounting<br />

the Unit to a DIN track.<br />

Terminal Block<br />

Used to connect <strong>CompoBus</strong>/S communications cables<br />

and communications power supply.<br />

I/O Indicators<br />

Indicate I/O status of each contact.<br />

The left half is lit when the input is ON, the<br />

right half is lit when the output is ON.<br />

Terminal Block<br />

The left half is the input terminal block<br />

and is used to connect I/O power<br />

supply, and input devices such as<br />

switches and sensors.<br />

The right half is the output terminal<br />

block and is used to connect I/O<br />

power supply, and output devices<br />

such as relays and indicators.<br />

Indicators<br />

The following table shows the meaning of the indicators.<br />

Indicator Status Meaning<br />

PWR (green) ON The communications power supply is ON.<br />

OFF The communications power supply is OFF.<br />

COMM (yellow) ON Normal communications<br />

OFF A communications error has occurred or the Unit is in<br />

standby status.<br />

ERR (red) ON A communications error has occurred.<br />

OFF Normal communications or the Unit is in standby status.<br />

0 to 7 (8 inputs) ON The corresponding input is ON.<br />

0 to 7 (8 outputs)<br />

(yellow)<br />

OFF The corresponding input is OFF or the Unit is in standby<br />

status.<br />