Connector Terminals Section 5-2<br />

Node number Setting (Hex) Node number Setting (Hex)<br />

0 0 8 8<br />

1 1 9 9<br />

2 2 10 A<br />

3 3 11 B<br />

4 4 12 C<br />

5 5 13 D<br />

6 6 14 E<br />

7 7 15 F<br />

Note 1. The node number of the 32-point Slave must be set to an even number. If<br />

an odd number is input, the odd number less one will be set in the Slave.<br />

2. The possible range of node numbers varies with the type of Master and<br />

settings in the Master. Refer to 2-1 Communications Specifications for details.<br />

Communications Mode Settings<br />

The following communications modes are set with pin 3 of the DIP switch as<br />

shown below.<br />

SW3 Communications<br />

mode<br />

OFF High-speed Communications<br />

Mode<br />

ON Long-distance<br />

Communications<br />

Mode<br />

Communications<br />

distance<br />

Communications<br />

baud rate<br />

Communications<br />

cycle time<br />

100 m max. 750 kbps 0.5 or 0.8 ms<br />

500 m max. 93.75 kbps 4.0 or 6.0 ms<br />

Note Make sure that the communications mode of the Slave is the same as that of<br />

the Master Unit. If the communications modes are not the same, normal communications<br />

with the Master Unit will not be possible. The operating status of<br />

the Slave can be verified with LED indicators. Refer to 6-5-1 Indicators.<br />

Hold/Clear Outputs for Communications Errors<br />

Pin 4 is used to set the output data status when a communications error<br />

occurs, as shown in the following table.<br />

Pin 4 (HOLD) Setting<br />

OFF Clear output status<br />

ON Maintain output status<br />

239