164<br />

Item Specification<br />

Node number settings The node number is set on a DIP switch. (Set the node<br />

number before turning ON the Slave.)<br />

Weight SRT@-OD04: 80 g max.<br />

SRT@-OD08: 80 g max.<br />

SRT@-OD16: 110 g max.<br />

SRT@-OD04-1: 80 g max.<br />

SRT@-OD08-1: 80 g max.<br />

SRT@-OD16-1: 110 g max.<br />

Note The current consumption is the value with all 4 and 8 and 16 points turned ON<br />

excluding the current consumption of the external sensor connected to the<br />

input Remote Terminal and the current consumption of the load connected to<br />

the output Remote Terminal.<br />

Output Specifications<br />

Item Specification<br />

Rated output current 0.3 A/point<br />

Residual voltage 0.6 V max.<br />

SRT@-OD@@: Between each output terminal and G<br />

SRT@-OD@@-1: Between each output terminal and V<br />

Leakage current 0.1 mA max.<br />

ON delay time 0.5 ms max.<br />

OFF delay time 1.5 ms max.<br />

Insulation method Photocoupler<br />

Output indicators LED (yellow)<br />

Slave Components The following diagram shows the main components of the SRT2-OD08 Transistor<br />

Remote Terminal. The functions of these components are described<br />

below.<br />

DIP Switch<br />

Open the cover to reveal the DIP switch. The DIP switch's<br />

pins have the following functions:<br />

Pin 1: Hold/clear outputs for communications error<br />

Pin 2: Communications mode setting (SRT2 Series)<br />

or Reserved (Always OFF) (SRT1 Series)<br />

Pins 3 to 6: Node number setting<br />

<strong>CompoBus</strong>/S Indicators<br />

Indicate the status of the Slave and communications.<br />

Mounting Screw Holes<br />

Used when screwing the Unit to a control panel.<br />

DIN Track Mounting Hook<br />

Used when mounting the Unit to a DIN track.<br />

Terminal Block<br />

Connect the <strong>CompoBus</strong>/S communications cable, communications<br />

power supply, I/O power supply, and output devices such as relays<br />

and indicators to the terminal block.<br />

Output Indicators<br />

Indicate the status of each contact.<br />

(Lit when the output is ON.)<br />

The SRT-OD04 and SRT-OD04-1 have 4 indicators,<br />

the SRT-OD08 and SRT-OD08-1 have 8 indicators, and<br />

the SRT-OD16 and SRT-OD16-1 have 16 indicators.