Checking Operations of CS-series and CJ-series Master Units Section 6-3<br />

Error Probable cause Possible remedy<br />

The Master Unit’s<br />

ERH indicator is<br />

ON<br />

A Slave Unit’s<br />

COMM indicator<br />

is OFF or its ERR<br />

indicator is ON<br />

The I/O table is not registered. Recreate the I/O tables.<br />

The same unit number has been set<br />

on another Special I/O Unit.<br />

The unit number has been set outside<br />

the specified range.<br />

The CPU Unit is faulty. Replace the CPU Unit.<br />

An error has occurred at the Master<br />

Unit.<br />

The Slave cannot participate in communications<br />

because its power supply<br />

is OFF. (The Slave’s PWR indicator is<br />

OFF.)<br />

The Slave cannot participate in communications<br />

because there is a problem<br />

with the Slaves’ power supply.<br />

The Slave cannot participate in communications<br />

because its power supply<br />

is inadequate.<br />

The Slave cannot participate in communications<br />

because there is a problem<br />

with the communication cable<br />

connection or the cable itself.<br />

The same node number is used on<br />

another Slave between inputs Slaves<br />

or between output Slaves.<br />

A Slave’s number has been set to 8 to<br />

15 even though the usable node number<br />

setting is IN0 to IN7 and OUT0 to<br />

OUT7.<br />

Communications modes of Master<br />

Unit and Slave do not match.<br />

A common system mistake has been<br />

made. (Refer to the table on page 376<br />

for a list of common mistakes.)<br />

Check that the same unit number is not used by more than<br />

one Special I/O Unit and turn the PLC OFF and ON again. In<br />

particular, when the usable node number setting is IN0 to<br />

IN15 and OUT0 to OUT15, check that the next unit number<br />

after the one set on the Master Unit is not set on another<br />

Special I/O Unit.<br />

Check that the unit number is set within the range specified<br />

for Special I/O Units and turn the PLC OFF and ON again.<br />

CS-series and CJ-series PLCs<br />

Unit numbers 0 to 95 can be set when the Master Unit is<br />

using 10 words as a single Special I/O Unit and the usable<br />

node number setting is IN0 to IN7 and OUT0 to OUT7 (DIP<br />

switch pin 1 OFF).<br />

Unit numbers 0 to 94 can be set when the Master Unit is<br />

using 20 words as two Special I/O Units and the usable node<br />

number setting is IN0 to IN15 and OUT0 to OUT15 (DIP<br />

switch pin 1 ON).<br />

Check the Master Unit’s indicators and follow the procedures<br />

listed above.<br />

Turn ON the Slave’s power supply.<br />

The Slave Unit is faulty. Replace the Slave Unit.<br />

The area used by the Analog Terminal<br />

or 32-point Connector Terminal<br />

exceeds the range of the Master Unit<br />

I/O Area.<br />

Check the power supply cable connections and connect the<br />

cables to the Slaves correctly.<br />

Check the power supply capacity. If it is inadequate, either<br />

change the system configuration or change the power supply<br />

so that sufficient power is provided.<br />

Check the connections and cable. Replace the communications<br />

cable if it is faulty.<br />

Change one of the Slave’s node number settings to eliminate<br />

the duplication and then turn the Slaves ON again. Either<br />

reset the Master Unit with the PLC’s Restart Bit or turn the<br />

PLC OFF and then ON again.<br />

Either change the Input and Output Slave’s node number settings<br />

so that they are 0 to 7 or change the usable node number<br />

setting to IN0 to IN15 and OUT0 to OUT15.<br />

Set the communications mode so that it is the same as that of<br />

the Master Unit.<br />

Refer to the table on page 376 for common mistakes and<br />

their remedies.<br />

Change to node numbers that do not exceed the I/O Area<br />

range, then turn ON the PLC again.<br />

375