Connector Terminals Section 5-2<br />

Is the input power supply<br />

voltage 20.4 to 26.4 V DC?<br />

Yes<br />

Do input specifications agree?<br />

Yes<br />

What is the size of the<br />

conductors in the cable?<br />

0.3 to 0.5 mm 2<br />

Compatible<br />

Use an XS8A-0441 Connector to<br />

connect the sensor.<br />

No<br />

No<br />

Incompatible<br />

Incompatible<br />

0.14 to 0.2 mm 2<br />

Compatible<br />

Use an XS8A-0442 Connector to<br />

connect the sensor.<br />

Note 1. The size of the sensor cable conductor is calculated as below.<br />

Conductor description of sensor cable:<br />

φ Outside diameter of cable (number of wires/wire diameter)<br />

conductor size (mm 2 )<br />

= (wire diameter/2) 2 × π × number of wires<br />

Example: E3S-A Sensor<br />

Incompatible<br />

φ 4 (18/0.12) → Conductor size (mm2 )<br />

= (0.12/2) 2 × 3.14 × 18 = 0.20<br />

Since the conductor size works out to be 0.2 mm2 , use XS8A-0442 Connector.<br />

2. The XS8A-0441 and XS8A-0442 Connectors are not provided with the<br />

Unit. The Connectors must be ordered separately.<br />

Models with MIL Connectors (SRT2-VID16ML-1)<br />

The MIL Connector can be connected to external devices using either of the<br />

following methods.<br />

1,2,3... 1. Using an XG4A-2030-T MIL Connector (sold separately) to Assemble Your<br />

Own Cable<br />

For details, refer to MIL Connector Wiring and Assembly on page 258.<br />

Insert with protrusion<br />

facing right.<br />