03.08.2013 Views

OPERATION MANUAL CompoBus/S

OPERATION MANUAL CompoBus/S

OPERATION MANUAL CompoBus/S

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Connector Terminals Section 5-2<br />

216<br />

Models with MIL Connectors<br />

SRT2-VOD16ML/VOD16ML-1<br />

Communications connector<br />

Used to connect <strong>CompoBus</strong>/S communications data (BD H, BD L), communications<br />

power supply, and I/O power supply (see page 256).<br />

One compatible connector is provided as standard.<br />

Indicators<br />

Indicate the status of the Slave and communications, and<br />

output status of each contact. (Lit when the output is ON.)<br />

View from (A) (base)<br />

DIN Track Mounting Hook<br />

DIP Switch<br />

The DIP switch's pins have the following functions:<br />

Pins 1 to 4: Node number setting<br />

Pins 5 and 6: Reserved (Always OFF.)<br />

Pin 7: Communications mode setting<br />

Pin 8: Hold/Clear outputs for communications error<br />

Output Connector (MIL Connector)<br />

Connect 16 outputs with MIL connector (see page 258).<br />

XG4M-2030-T MIL Connector and compatible cable are sold separately.<br />

Indicators<br />

The following table shows the meaning of the indicators.<br />

Indicator Status Meaning<br />

PWR (green) ON The communications power supply is ON.<br />

OFF The communications power supply is OFF.<br />

COMM (yellow) ON Normal communications<br />

OFF A communications error has occurred or the Unit is<br />

in standby status.<br />

ERR (red) ON A communications error has occurred.<br />

OFF Normal communications or the Unit is in standby status.<br />

0 to 7 (8 outputs) ON The corresponding output is ON.<br />

0 to 15 (16 outputs)<br />

OFF The corresponding output is OFF or the Unit is in<br />

standby status.<br />

DIP Switch<br />

The DIP switch is located on the base of the Connector Terminal.<br />

Hold/Clear outputs for communications error<br />

Communications mode setting<br />

Reserved (Always OFF.)<br />

Node number setting<br />

Note Always turn OFF the Slave before changing DIP switch settings.