Sensor Amplifier Terminals Section 5-11<br />

Note The actual node number setting range depends on the type of PLC in which<br />

the Master is mounted as well as the Master’s settings. Refer to 2-1 Communications<br />

Specifications for details.<br />

Internal Circuits The following diagram shows the internal circuits for the E39-JID01.<br />

Terminal Arrangement<br />

and Wiring<br />

Node number Pin 1 Pin 2 Pin 4 Pin 8<br />

(1) (2) (4) (8)<br />

3 ON ON OFF OFF<br />

4 OFF OFF ON OFF<br />

5 ON OFF ON OFF<br />

6 OFF ON ON OFF<br />

7 ON ON ON OFF<br />

8 OFF OFF OFF ON<br />

9 ON OFF OFF ON<br />

10 OFF ON OFF ON<br />

11 ON ON OFF ON<br />

12 OFF OFF ON ON<br />

13 ON OFF ON ON<br />

14 OFF ON ON ON<br />

15 ON ON ON ON<br />

Internal Circuitry<br />

The following diagram shows the terminal arrangement and wiring for the<br />

E39-JID01.<br />

3-wired Sensor 2-wired Sensor<br />

Black<br />

Brown<br />

Blue<br />

Sensor<br />

Brown<br />

Blue<br />

Sensor<br />