Remote Terminals Section 5-1<br />

Indicator Status Meaning<br />

COMM (yellow) ON Normal communications<br />

OFF A communications error has occurred or the Unit is in<br />

standby status.<br />

ERR (red) ON A communications error has occurred.<br />

OFF Normal communications or the Unit is in standby status.<br />

0 to 15 (yellow) ON The corresponding input is ON.<br />

OFF The corresponding input is OFF or the Unit is in standby<br />

status.<br />

Switch Settings Rotary and DIP switches are used to enter settings.<br />

Rotary Switch<br />

Node number setting<br />

Reserved<br />

(Always OFF)<br />

DIP Switch<br />

Reserved (Always OFF)<br />

Communications mode setting<br />

(SRT2 Series)<br />

or Reserved (Always OFF)<br />

(SRT1 Series)<br />

Note 1. Always turn OFF the Slave before changing DIP switch settings.<br />

2. In the SRT1 Series, pin 3 must always be left OFF. Otherwise, the Unit may<br />

not function correctly.<br />

3. All pins marked “RSV” (reserved) must be left OFF. If any of them is ON,<br />

the Unit may not function correctly.<br />

Node Number Settings<br />

The rotary switch specifies node numbers as hexadecimal numbers, as<br />

shown below.<br />

Node number Setting<br />

(Hexadecimal)<br />

Node number Setting<br />

(Hexadecimal)<br />

0 0 8 8<br />

1 1 9 9<br />

2 2 10 A<br />

3 3 11 B<br />

4 4 12 C<br />

5 5 13 D<br />

6 6 14 E<br />

7 7 15 F<br />

Note 1. Node numbers of 16-point Slaves are always treated as even numbers.<br />

Even if an odd number is specified, the actual node number setting becomes<br />

the even number immediately preceding it.<br />

2. The actual node number setting range depends on the type of PLC in<br />

which the Master is mounted as well as the Master’s settings. Refer to 2-1<br />

Communications Specifications for details.<br />