Remote Terminals Section 5-1<br />

182<br />

Switch Settings<br />

Rotary and DIP switches are used to enter settings.<br />

Rotary Switch DIP Switch<br />

Node number setting<br />

Reserved<br />

(Always OFF)<br />

Hold/Clear outputs for<br />

communications error<br />

Communications mode<br />

setting (SRT2 Series)<br />

or<br />

Reserved (Always OFF)<br />

(SRT1 Series)<br />

Note 1. Always turn the Slave OFF before changing DIP switch settings.<br />

2. In the SRT1 Series, pin 3 must always be left OFF. Otherwise, the Unit may<br />

not function correctly.<br />

3. All pins marked “RSV” (reserved) must be left OFF. If any of them is ON,<br />

the Unit may not function correctly.<br />

Node Number Settings<br />

The rotary switch specifies node numbers as hexadecimal numbers, as<br />

shown below.<br />

Node number Setting<br />

(Hexadecimal)<br />

Node number Setting<br />

(Hexadecimal)<br />

0 0 8 8<br />

1 1 9 9<br />

2 2 10 A<br />

3 3 11 B<br />

4 4 12 C<br />

5 5 13 D<br />

6 6 14 E<br />

7 7 15 F<br />

Note 1. A 16-point I/O Slave is handled as a single 8-point Input Slave and a single<br />

8-point Output Slave that possess the same node number.<br />

2. The actual node number setting range depends on the type of PLC in<br />

which the Master is mounted as well as the Master’s settings. Refer to 2-1<br />

Communications Specifications for details.<br />

Communications Mode Settings (SRT2 Series Only)<br />

The communications mode is set with pin 3, as shown below.<br />

Pin 3 CommunicaCommunicaCommunicaCommunications mode tions distance tions baud rate tions cycle time<br />

OFF High-speed Communications<br />

Mode<br />

100 m max. 750 kbps 0.5 or 0.8 ms<br />

ON Long-distance<br />

Communications<br />

Mode<br />

500 m max. 93.75 kbps 4.0 or 6.0 ms<br />

The communications mode settings using pin 3 only apply to the SRT2 Series<br />

and cannot be used with the SRT1 Series, which operate in High-speed Communications<br />

Mode at all times.