Checking Operations of CS-series and CJ-series Master Units Section 6-3<br />

TST (350)<br />

D20004<br />

#F<br />

TST (350)<br />

D20004<br />

#0<br />

d c<br />

Registered<br />

Slaves joined<br />

network<br />

Bit 15 (Error Flag)<br />

6-3-5 Troubleshooting<br />

Operations<br />

Bit 00 (Registration Completed Flag)<br />

Error<br />

detected<br />

Slave I/O processing program<br />

c<br />

Error detected<br />

d<br />

Registered<br />

Slaves joined<br />

network<br />

JMP (004)<br />

#0002<br />

JME (005)<br />

#0002<br />

When bit 15 of D20004 is ON, work bit c<br />

(error detected) turns ON.<br />

When bit 00 of D20004 is ON, work bit d<br />

(registered Slaves joined network) turns<br />

ON.<br />

Slave I/O is processed when JMP condition<br />

is ON only.<br />

If the JMP condition is OFF, the program<br />

jumps to JME and Slave I/O is not<br />

processed.<br />

When an error occurs, the indicators of the Master Unit connected to a CSseries<br />

or CJ-series PLC will indicate the error. Check the Master Unit's indicators<br />

and perform the error processing described in the following table.<br />

When an error occurs in a Slave, the Slave can be identified from the status of<br />

the Master’s indicators (refer to page 76) or from the status flags (refer to<br />

page 365) in the PLC’s Special I/O Unit Area.<br />

Error Probable cause Possible remedy<br />

The Master Unit’s<br />

RUN indicator is<br />

OFF<br />

The PLC’s power is OFF. Turn the PLC’s power supply ON.<br />

The same unit number has been set<br />

on another Special I/O Unit, causing<br />

an area overlap error in the PLC.<br />

The unit number has been set outside<br />

the specified range, causing an area<br />

overlap error in the PLC.<br />

The usable node number setting was<br />

changed with the PLC power ON, and<br />

the Master Unit was restarted only.<br />

A Special I/O Unit error occurred in<br />

the PLC because the Master Unit is<br />

not connected securely.<br />

Check that the same unit number is not used by more than<br />

one Special I/O Unit and restart the PLC. In particular, when<br />

the usable node number setting is IN0 to IN15 and OUT0 to<br />

OUT15, check that the next unit number after the one set on<br />

the Master Unit is not set on another Special I/O Unit.<br />

Check that the unit number is set within the range specified<br />

for Special I/O Units and restart the PLC.<br />

CS-series and CJ-series PLCs<br />

Unit numbers 0 to 95 can be set when the Master Unit is<br />

using 10 words as a single Special I/O Unit and the usable<br />

node number setting is IN0 to IN7 and OUT0 to OUT7 (DIP<br />

switch pin 1 OFF).<br />

Unit numbers 0 to 94 can be set when the Master Unit is<br />

using 20 words as two Special I/O Units and the usable node<br />

number setting is IN0 to IN15 and OUT0 to OUT15 (DIP<br />

switch pin 1 ON).<br />

Turn the PLC OFF and then ON again, and recreate the I/O<br />

tables.<br />

Turn the PLC OFF, make sure that the Master Unit is<br />

mounted correctly, and then turn the PLC ON again. Replace<br />

the Master Unit if the error recurs.<br />

The Master Unit is faulty. Replace the Master Unit.<br />

Communications stop mode is set. Communications stop when a communications error occurs<br />

in communications stop mode. Remove the cause of the<br />

error, and then reset the Master Unit using the PLC’s Restart<br />

Bit or turn the PLC OFF and then ON again.<br />

373