Cleaning and Inspection Section 6-6<br />

6-6 Cleaning and Inspection<br />

6-6-1 Cleaning<br />

6-6-2 Inspection<br />

384<br />

This section describes the routine cleaning and inspection recommended as<br />

regular maintenance.<br />

Clean the <strong>CompoBus</strong>/S regularly as described below in order to keep it in its<br />

optimal operating condition.<br />

Wipe the Unit with a dry, soft cloth for regular cleaning.<br />

When a spot cannot be removed with a dry cloth, dampen the cloth with a<br />

neutral cleanser, wring out the cloth, and wipe the Unit.<br />

A smudge may remain on the Unit from gum, vinyl, or tape that was left on<br />

for a long time. Remove the smudge when cleaning.<br />

!Caution Never use volatile solvents such as paint thinner or benzene or chemical<br />

wipes. These substances could damage the surface of the Unit.<br />

Be sure to inspect the system periodically to keep it in optimal operating condition.<br />

In general, inspect the system once every 6 to 12 months, but inspect<br />

more frequently if the system is used with high temperature or humidity or<br />

under dirty/dusty conditions.<br />

Inspection Equipment Prepare the following equipment before inspecting the system.<br />

Required Equipment<br />

Have a standard and phillips screwdriver, multimeter, alcohol, and a clean<br />

cloth.<br />

Equipment that Could be Needed<br />

Depending on the system conditions, you might need a synchroscope, oscilloscope,<br />

thermometer, or hygrometer (to measure humidity).<br />

Inspection Procedure Check the items in the following table and correct any items that are below<br />

standard.<br />

Item Standard Equipment<br />

Environmental Ambient and cabinet temperature See below. Thermometer<br />

conditions Ambient and cabinet humidity See below. Hygrometer<br />

Dust/dirt accumulation None Visual inspection<br />

Installation Are the Units mounted securely? No looseness Phillips screwdriver<br />

Are the connecting cable connec- No looseness Phillips screwtors<br />

fully inserted?<br />

driver<br />

Are the external wiring screws No looseness Phillips screw-<br />

tight?<br />

driver<br />

Are the connecting cables undam- No damage Visual inspecaged?tion<br />

The following table shows the acceptable operating temperature and operating<br />

humidity ranges for <strong>CompoBus</strong>/S Units.<br />

Unit Acceptable temperature Acceptable humidity*<br />

Master Unit 0 to 55°C 10% to 90%<br />

Remote Terminal 0 to 55°C 35% to 85%<br />

Remote I/O Module 0 to 55°C 35% to 85%<br />

Sensor Amplifier Terminal 0 to 55°C 35% to 85%