System Configuration Section 2-2<br />

Slave<br />

Main line<br />

2-2-2 Maximum Cable Length<br />

tidrop method. When the main line is distinguished from branch lines, Slaves<br />

must be connected to the main line.<br />

System with Distinction between<br />

Main and Branch Lines<br />

Master<br />

Branch line length<br />

L 1<br />

System with No Distinction between<br />

Main and Branch Lines<br />

Node<br />

Cable<br />

The actual wiring for multidrop connections is shown in the following diagram.<br />

The Slave is connected to the signal wires from the Master side of the system<br />

as well as the signal wires from the terminator side of the system.<br />

Main line cable from the<br />

Master or previous Slave<br />

Connects to the Connects to the<br />

Slave's BD L terminal. Slave's BD H terminal.<br />

Communications cable<br />

Low side (BD L)<br />

Communications cable<br />

High side (BD H)<br />

Main line cable to the<br />

next Slave or terminator<br />

The main line length is the total length of the cable connecting the Master and<br />

the terminator at the farthest end of the system. The branch line length is the<br />

length of a cable connecting a Slave to the main line and the total branch line<br />

length is the sum of lengths of all of the branch lines in the system.<br />

When the system has no main line distinguished from the branch lines, the<br />

communications cable can be connected with no particular restrictions, provided<br />

that the total length of communications cable is a maximum of 200 m.<br />

Main line<br />

Slave Slave L3 L4 Slave<br />

L5 Slave Slave Slave Slave Slave<br />

Total branch line length = L 1 + L 2 + L 3 + L 4 + L 5<br />

Communication<br />

mode<br />

High-speed Communications<br />

Mode<br />

L 2<br />

Terminator<br />

The maximum main line, branch line, total branch line, and total cable lengths<br />

depend on the type of cable and number of Slaves being used, as shown in<br />

the following table.<br />

Cable type Cable length<br />

Main line Branch line Total of branch lines<br />

2-conductor VCTF cable 100 m max. 3 m max. 50 m max.<br />

4-conductor VCTF cable 30 m max.<br />

(See note.)<br />

Flat 30 m max.<br />

(See note.)<br />

3 m max. 30 m max.<br />

(See note.)<br />

3 m max. 30 m max.<br />

(See note.)<br />

29