Master/Slave Connecting Cables Section 3-4<br />

Terminal-block<br />

Terminators<br />

66<br />

When the VCTF cable is connected to an SRS1-T Terminal-block Terminator,<br />

use crimp terminals on each of the BD H and BD L signal wires, and connect<br />

them to each terminal. The signal wires can be connected to any of the terminals.<br />

Note 1. Do not connect both signal wires to a single terminal.<br />

2. When connecting the communications power supply using Special Flat<br />

Cable or 4-conductor VCTF cable, insulate the BD+ and BS– power supply<br />

cables.<br />

Tighten the terminal screws to the specified tightening torque (0.3 to<br />

0.5 N⋅m).<br />

3. When connecting Terminal-block Terminators to VCTF cables, use the<br />

same crimp terminals as those used to connect the communications cables<br />

to the Slaves. (Refer to 3-4 Master/Slave Connecting Cables.)<br />

Shield Terminators When using 4-conductor VCTF cable, terminators can be connected by connecting<br />

an SRS2-1 Shield Terminator to the T-joint.<br />

Note The SRS2-1 Shield Connector has a male plug. Connect it to the female<br />

socket connector of the T-joint.<br />

3-4 Master/Slave Connecting Cables<br />

3-4-1 Crimp Terminal Installation<br />

This section describes the methods used for connecting communications<br />

cables to each device and installing connectors on the Connector Terminal<br />

and Sensor Terminal cables.<br />

Attach crimp terminals to the ends of the communications cable when connecting<br />

the cable to a Master, Slave, Terminal-block Terminator, or commercially<br />

available terminal block.<br />

!Caution Do not connect bare signal wires to the terminals since the wires could short<br />

and damage the Unit to which they are connected.<br />

Note Do not strip too much insulation from the wires when preparing the cable for<br />

the crimp terminals. Cover the shaft of the terminal connector and the end of<br />

the wire with electrical tape or heat-shrinking tube.<br />

Master or Slave When connecting communications cable (VCTF cable or Special Flat Cable)<br />

to a Master or Slave, attach an M3 crimp terminal like those shown below to<br />

each signal wire.<br />

M3 Terminals for the Master Unit (Except CJ Series)<br />

6.2 mm max. 6.2 mm max.<br />

Recommended terminal Comment<br />

Nippon Crimp Terminal 1.25-N3A Forked terminal<br />

Molex Y1.25-3.5L Forked terminal<br />

Note Refer to 4-3-3 Wiring and Installing Communications Cables for details on<br />

crimp terminals used for connecting CJ-series Master Units.