C200HW-SRM21-V1 Master Unit for CS-series, C200HX/C200HG/C200HE-(Z)E, and C200HS PLCsSection 4-1<br />

78<br />

The Master Unit is factory-set to OFF (for IN0 to IN7 and OUT0 to OUT7).<br />

The maximum number of Slaves setting affects both the total number of<br />

words allocated and the Slaves’ communication cycle. Refer to 4-1-3 I/O<br />

Allocations in CS-series, C200HX/C200HG/C200HE-(Z)E, and C200HS<br />

PLCs for details.<br />

The Master Unit is allocated twice as many words in the PLC’s Special I/O<br />

Unit Area (the words for unit number set on the Master and the next unit<br />

number) when the usable node number setting is set to IN0 to IN15 and<br />

OUT0 to OUT15. In this case, neither the Master’s unit number nor the<br />

next unit number can be used on another Special I/O Unit mounted in the<br />

PLC.<br />

Pin 2 is factory-set to OFF (High-speed Communications Mode).<br />

The setting of pin 2 determines the communications distance, baud rate,<br />

and cycle time as shown in the above table.<br />

4-1-3 I/O Allocations in CS-series, C200HX/C200HG/C200HE-(Z)E, and<br />

C200HS PLCs<br />

Allocations and Master<br />

Unit Settings<br />

In CS-series, C200HX/C200HG/C200HE-(Z)E, and C200HS PLCs, the Master<br />

Unit is treated as a Special I/O Unit, so the Slave’s I/O data and status<br />

information are stored in the sections of the PLC’s data areas which are allocated<br />

to Special I/O Units.<br />

The following settings affect I/O allocations to Slaves in the Master Units used<br />

with CS-series, C200HX/C200HG/C200HE-(Z)E, and C200HS PLCs.<br />

Setting at Master<br />

Unit<br />

Usable node number<br />

settings (DIP<br />

switch pin 1)<br />

Unit number setting<br />

(rotary switch)<br />

Status Affect on allocation<br />

OFF Uses 10 words (for one unit number) from the Special<br />

I/O Unit Area as follows:<br />

Output: 4 words, input: 4 words, status: 2 words.<br />

ON Uses 20 words (for two unit numbers) from the Special<br />

I/O Unit Area as follows:<br />

Output: 8 words, input: 8 words, status: 4 words.<br />

n First word of the area used in the Special I/O Unit Area<br />

CS Series<br />

2000 + n × 10<br />

C200HX/HG/HE/HS<br />

For 0 ≤ n ≤ 9: 100 + n × 10<br />

For 10 ≤ n ≤ 15 (A to F): 400 + (n − 10) × 10<br />

Slave Allocations Slaves are allocated words in the Special I/O Unit Area as described next. In<br />

<strong>CompoBus</strong>/S Systems, node numbers of Input Slaves and Output Slaves are<br />

treated separately so the same node number can be allocated.<br />

I/O Allocations when Pin 1 Is OFF<br />

When pin 1 is OFF and node addresses IN0 to IN7 and OUT0 to OUT7 (up to<br />

64 inputs/64 outputs) are used, words are allocated to the Slaves for each<br />

node number as shown in the following diagrams.