Hardware Installation, Deinstallation and Replacement 135/274<br />
5.12.3 Installing CIFX 104-RE\F and CIFX 104-RE-R\F<br />
To install the<br />
• CIFX 104-RE\F <strong>Communication</strong> Interface PC/104(„\F“) and<br />
• CIFX 104-RE-R\F <strong>Communication</strong> Interface PC/104(„\F“)<br />
handle as follows:<br />
1. Configure starting address, interrupt and data bus width of the CIFX<br />
104-RE\F <strong>Communication</strong> Interface.<br />
‣ Configure the start address of the CIFX 104-RE\F.<br />
‣ If you are using the interrupt mode, set up a free interrupt on the CIFX<br />
104-RE\F.<br />
For polling operation mode interrupt jumpers are not required.<br />
Note: Several CIFX 104-RE\F <strong>Communication</strong> <strong>Interfaces</strong> can be plugged<br />
as modules one upon the other. For each CIFX 104-RE\F <strong>Communication</strong><br />
Interface you must define a free memory area of 16 KByte.<br />
For further information on the starting address and or an interrupt (or<br />
polling) refer to section <strong>cifX</strong> PC/104: Set Starting Address and Interrupt on<br />
page 124.<br />
‣ Depending by the target system (motherboard), if so, set at the CIFX<br />
104-RE\F a Data Bus Width of 8 bit or 16 bit.<br />
By default the jumper is set for a data bus width of 16 Bit (refer to section<br />
Device Drawing CIFX 104-RE\F on page 133 and Device Drawing CIFX<br />
104-RE-R\F on page 134).<br />
2. Take safety precautions.<br />
Lethal Electrical Shock caused by parts with more than 50V!<br />
• Disconnect the power plug of the PC or of the connecting device.<br />
• Make sure, that the power supply is off at the PC or at the connecting<br />
device.<br />
3. Open cabinet.<br />
‣ Open the cabinet of the PC or of the connecting device.<br />
Note: If several CIFX 104-RE\F <strong>Communication</strong> <strong>Interfaces</strong> are to be put<br />
together as modules in a stack:<br />
(a) Install the first <strong>cifX</strong> on the mainboard.<br />
(b) Connect the AIFX-RE or the AIFX-DIAG to the <strong>cifX</strong>.<br />
(e) Connect any other module in the same way (as a and b).<br />
For more see next page.<br />
<strong>cifX</strong> <strong>Communication</strong> <strong>Interfaces</strong> <strong>Ethernet</strong> | Installation, Operation and Hardware Description<br />
DOC060501UM30EN | Revision 30 | English | 2011-06 | Released | Public © <strong>Hilscher</strong>, 2006-2011