Technical Data 250/274<br />

10.3.3 EtherNet/IP Scanner (Master)<br />

Parameter<br />

Maximum number of EtherNet/IP connections<br />

Maximum number of total cyclic input data<br />

Maximum number of total cyclic output data<br />

Maximum number of cyclic input data<br />

Maximum number of cyclic output data<br />

Description<br />

64 connections for implicit and explicit<br />

5712 bytes<br />

5760 bytes<br />

504 bytes per slave per telegram<br />

504 bytes per slave per telegram<br />

IO Connection type<br />

Cyclic, minimum 1 ms (depending on used number of connections<br />

and used number of input and output data)<br />

Maximum number of unscheduled data<br />

1400 bytes per telegram<br />

UCMM, Class 3<br />

Supported<br />

Explicit Messages, Client and Server Services Get_Attribute_Single/All<br />

Set_Attribute_Single/All<br />

Predefined standard objects<br />

Identity Object<br />

Message Route Object<br />

Assembly Object<br />

Connection Manager<br />

<strong>Ethernet</strong> Link Object<br />

TCP/IP Object<br />

Maximal number of user specific objects 20<br />

Topology<br />

Tree, Line, Ring<br />

DLR (Device Level Ring)<br />

Beacon based ’Ring Node’<br />

ACD (Address Conflict Detection)<br />

Supported<br />

DHCP<br />

Supported<br />

BOOTP<br />

Supported<br />

Baud rates<br />

10 and 100 MBit/s<br />

Data transport layer <strong>Ethernet</strong> II, IEEE 802.3<br />

Integrated switch<br />

Supported<br />

Limitations<br />

CIP Sync Services are not implemented<br />

TAGs are not supported<br />

Reference to firmware/stack version<br />

V2.4.x.x<br />

Table 99: Technical Data EtherNet/IP Scanner (Master) Protocol<br />