Technical Data 255/274<br />

10.3.8 PROFINET IO-RT-Device<br />

Parameter<br />

Maximum number of cyclic input data<br />

Maximum number of cyclic output data<br />

Acyclic communication<br />

Alarm Types<br />

Description<br />

1024 bytes<br />

1024 bytes<br />

Read/Write Record, max. 1024 bytes per telegram<br />

Process Alarm, Diagnostic Alarm, Return of SubModule Alarm<br />

Supported protocols<br />

RTC – <strong>Real</strong> <strong>Time</strong> Cyclic Protocol, Class 1 and 2 (unsynchronized), Class<br />

3 (synchronized)<br />

RTA – <strong>Real</strong> <strong>Time</strong> Acyclic Protocol<br />

DCP – Discovery and configuration Protocol<br />

CL-RPC – Connectionless Remote Procedure Call<br />

LLDP – Link Layer Discovery Protocol<br />

SNMP – Simple Network Management Protocol<br />

Used Protocols (subset)<br />

UDP, IP, ARP, ICMP (Ping)<br />

Topology recognition<br />

LLDP, SNMP V1, MIB2, physical device<br />

VLAN- and priority tagging<br />

yes<br />

Context Management by CL-RPC Supported<br />

Identification & Maintenance<br />

Read and write of I&M1-4<br />

Minimum cycle time<br />

1 ms for RTC1 and RTC2<br />

250 µs for RTC3<br />

Baud rate<br />

100 MBit/s<br />

Data transport layer <strong>Ethernet</strong> II, IEEE 802.3<br />

Limitations<br />

RT over UDP not supported<br />

Multicast communication not supported<br />

Only one device instance is supported<br />

DHCP is not supported<br />

IRT “flex” (synchronized RT Class 2) is not supported<br />

FastStartUp is not supported.<br />

Media Redundancy (except MRP client) is not supported<br />

Access to the submodule granular status bytes (IOCS) is not supported.<br />

The amount of configured IO-data influences the minimum cycle time<br />

that can be reached.<br />

Supervisor-AR is not supported, Supervisor-DA-AR is supported<br />

Only 1 Input-CR and 1 Output-CR are supported<br />

Multiple WriteRequests are not supported<br />

Using little endian (LSB-MSB) byte order for cyclic process data instead<br />

of default big endian (MSB-LSB) byte order may have an negative impact<br />

on minimum reachable cycle time<br />

Reference to firmware/stack version V3.4.x.x<br />

Table 104: Technical Data PROFINET IO RT IRT Device Protocol<br />