Device Connections and Switches 220/274<br />
9.3.3 Use of Hubs and Switches<br />
For the corresponding communication systems, the use of hubs and/or<br />
switches is either forbidden or allowed. The following table shows the<br />
acceptable use of hubs and switches by each communication system:<br />
<strong>Communication</strong> System Hub Switch<br />
EtherCAT forbidden only allowed between EtherCAT Master<br />
and first EtherCAT Slave<br />
(100 MBit/s, Full Duplex)<br />
EtherNet/IP allowed allowed<br />
(10 MBit/s/100 MBit/s,<br />
Full or Half Duplex, Auto-Negotiation)<br />
Open Modbus/TCP allowed allowed<br />
(10 MBit/s/100 MBit/s,<br />
Full or Half Duplex, Auto-Negotiation)<br />
POWELINK allowed forbidden<br />
PROFINET IO RT forbidden Only allowed, if the switch supports<br />
‚Priority Tagging’ and LLDP<br />
(100 MBit/s, Full Duplex)<br />
SERCOS III forbidden forbidden<br />
Table 67: Use of Hubs and Switches<br />
NOTICE!<br />
Failure of the Network <strong>Communication</strong><br />
• Do not operate hardware with the communication controllers netX 50,<br />
netX100 or netX 500 with the protocols <strong>Ethernet</strong> TCP/UDP/IP,<br />
EtherNet/IP or Modbus TCP at 10 MBit/s in half-duplex mode, otherwise<br />
failure of the network communication can occur.<br />
• Use only switches or 10/100 MBit/s dual-speed hubs and ensure that<br />
the network operates at 100 MBit/s and in full-duplex mode.<br />
Failure of the Network <strong>Communication</strong><br />
• Do not operate hardware with the communication controllers netX 50,<br />
netX100 or netX 500 with the protocols <strong>Ethernet</strong> TCP/UDP/IP,<br />
EtherNet/IP or Modbus TCP at 10 MBit/s in half-duplex mode, otherwise<br />
failure of the network communication can occur.<br />
• Use only switches or 10/100 MBit/s dual-speed hubs and ensure that<br />
the network operates at 100 MBit/s and in full-duplex mode.<br />
For further information refer to section Failure in 10 MBit/s Half Duplex<br />
Mode and Workaround on page 199.<br />