5. Network Installation Summary<br />

<strong>The</strong> following section is a summary <strong>of</strong> installation requirements. <strong>The</strong>se items are discussed in more<br />

detail throughout this document.<br />

5.1 Building Connectivity<br />

<strong>The</strong> <strong>City</strong> employs various communication services <strong>for</strong> building connectivity. <strong>The</strong> following<br />

communications services are commonly used:<br />

Carrier-based (Telco) Point to Point T-1<br />

Carrier-based cable modem service<br />

Carrier-based Ethernet with a copper 8PC hand<strong>of</strong>f<br />

Carrier-based Ethernet with a multi-mode (LC) hand<strong>of</strong>f<br />

Private Ethernet with a copper 8PC hand<strong>of</strong>f<br />

Private Ethernet with a multi-mode fiber (LC, SC, and ST) hand<strong>of</strong>f<br />

Private Ethernet with a single-mode fiber (LC, SC, and ST) hand<strong>of</strong>f<br />

Private Optical (OC-48, OC-192) fiber with single mode fiber (LC, SC) hand<strong>of</strong>f<br />

5.2 MDF/IDF Room Architecture<br />

A MDF/IDF Room provides a controlled environment to house telecommunications equipment and<br />

connecting hardware. It is also the demarcation point <strong>for</strong> all Facility, Backbone, Riser and horizontal<br />

cabling. This room is not to be shared with Electrical service, Security, Paging, Video Surveillance or<br />

alarm systems. This room should be located as close to the center <strong>of</strong> the building as possible.<br />

<strong>The</strong> minimum dimensions <strong>for</strong> the MDF/IDF is 6’ x 8’ with a 9’ ceiling and a 36” door opening<br />

outward. This room will support up to 80 <strong>City</strong> Personnel.<br />

For buildings that house more than 80 people the minimum MDF/IDF size shall increase to 10’ x<br />

10’with a 9’ ceiling and an outward swing 36” door. ITSD should be contacted during the design phase<br />

to determine final room layout.<br />

On buildings requiring a MDF and one or more IDF’S the distance between rooms should be limited to<br />

180 meters.<br />

Within this document there are “rules” and “guidelines”. <strong>The</strong> rules shall be followed precisely, while<br />

the guidelines should be applied using common sense and improvising where necessary.<br />

5.2.1 Plywood Backboard<br />

One wall in any MDF/IDF will be completely covered with ¾” fire rated plywood with stamps<br />

visible <strong>for</strong> inspection and if possible placed on a permanent wall and no more than 12” above<br />