Technical Requirements<br />

Instructional Space<br />

GENERAL CLASSROOM - RESTROOM (IS-01D)<br />

ROOM FUNCTION<br />

This space will provide toilet and lavatory facilities <strong>for</strong> the children<br />

receiving instruction in the General Classroom. (1) Sink<br />

and (1) toilet are required per 17 students. (3) fixtures, total,<br />

are required between (2) General Classrooms.<br />

ROOM DATA<br />

Net Square Feet (ASF)<br />

Avg. No. <strong>of</strong> Occupants<br />

No. <strong>of</strong> Spaces by Type<br />

110 asf Total Shared (55 asf ea.)<br />

n/a<br />

12.5 (Eastside); 12.5 (Westside)<br />

TECHNICAL REQUIREMENTS<br />

ARCHITECTURAL<br />

Floor<br />

Resil. Flooring or Ceramic Tile<br />

Base<br />

Rubber<br />

Walls See Note 3<br />

Ceiling<br />

Acoustical Tile System<br />

Lighting<br />

Fluorescent<br />

<strong>SA</strong>MPLE ROOM LAYOUT<br />

This diagram is included as a planning tool to ensure that the space<br />

will function as the users require within the assigned square feet. It is<br />

not intended to dictate the final design or configuration <strong>of</strong> the space.<br />

MECHANICAL / PLUMBING<br />

Temperature/Humidity Variable 68°f to 75°f @ 50%rh<br />

Air Changes/Hour min. per Code<br />

Hot Water (HW) X Cold Water (CW) X<br />

Other See Notes 4 and 5<br />

ELECTRICAL / COMMUNICATIONS<br />

Power 110v/20a/1-phase - See Note 6<br />

Dedicated Circuits<br />

Data<br />

Other<br />

Stand-by Power<br />

FURNISHINGS, FIXTURES & EQUIPMENT<br />

NOTES (CONTINUED)<br />

(2) Standard Flush Toilets cfci 3. Install ceramic tile wainscot to 5’-0” aff at walls or to ceiling<br />

(1) Standard Flush Toilet (ADA) cfci<br />

behind toilets. Utilize standard toilet compartment partitions<br />

between stalls. Partitions may extend to the floor <strong>for</strong> privacy<br />

Toilet Compartment Partitions <strong>for</strong> (3) Stalls<br />

cfci<br />

but should allow <strong>for</strong> caregiver supervision, as needed, <strong>of</strong><br />

Built-In Counter Surface with Lower Cabinets and<br />

(2) Sinks (Child Height) - (1) Sink to be ADA cfci<br />

the child. Install painted gypsum wallboard at all other wall<br />

locations.<br />

Wall-Mounted Mirror (Above Counter)<br />

cfci<br />

4. Provide plumbing <strong>for</strong> hot and cold water to sinks. (3) Sinks<br />

are required between the (2) General Classrooms to accommodate<br />

(1) Paper Towel Dispenser (Wall Mounted) cfci<br />

40 children. At least (1) sink should be located in the<br />

(1) Soap Dispenser (Wall Mounted) cfci Instructional Area. <strong>The</strong> remaining (2) sinks should be located<br />

NOTES<br />

within the Restroom to promote hand-washing.<br />

5. Provide plumbing <strong>for</strong> (3) flush toilets.<br />

1. Reference “Code and Standards” chapter <strong>for</strong> in<strong>for</strong>mation<br />

regarding additional design requirements <strong>of</strong> this space which<br />

may not be listed here.<br />

2. Space will be shared between (2) General Classrooms and<br />

should be located adjacent to and accessible from the Instructional<br />

Area. When combined, each Restroom will total 110 asf<br />

to accommodate the required number <strong>of</strong> fixtures (toilets and<br />

sinks) between both classrooms <strong>for</strong> 40 students.<br />

6. Convenience duplex GFCI power outlets shall be provided<br />

along the perimeter walls at regular intervals, in accordance<br />

with Code. When locating power outlets, pay special attention<br />

to the possible location <strong>of</strong> equipment.<br />

7. Cabinets shall be installed with either key lock or child-safety<br />

latches to prevent children access to materials within cabinets.<br />

If keyed, all cabinets shall be keyed with the same lock.<br />

8. This space does not require natural light.<br />

Facility <strong>Programming</strong> and Consulting<br />

An Architectural Space Program <strong>for</strong> the <strong>City</strong> <strong>of</strong> <strong>San</strong> <strong>Antonio</strong><br />

Final - May 2013<br />

<strong>Pre</strong>-K 4 <strong>SA</strong> Early Childhood Centers - East and Westside Centers<br />

Page 4.9