5.6 Quality Assurance<br />

This section describes the quality assurance procedure <strong>for</strong> MDF/IDF rooms.<br />

5.6.1 Acceptance Procedure<br />

An ITSD Cabling Plant Project Manager or designated representative shall inspect MDF/IDF<br />

rooms during new building construction or when cable and equipment work is done. Prior to<br />

any MDF/IDF room being accepted, all work shall meet engineering specifications, or<br />

appropriate standards stated within this document, or the current issue <strong>of</strong> Copper Wire and<br />

Cable Engineering Standards Procedure 201.16. For cable work, all installed pairs shall be<br />

tested using appropriate test equipment and the reading will be retained as a benchmark. For<br />

cable pair acceptance, all installed pairs shall be tested according to Engineering guidelines. All<br />

pairs shall be good and usable, with no defects.<br />

5.7 Wiring Specifications<br />

All wiring is to be installed according to the EIA/TIA wiring codes and shall adhere to all local wiring<br />

codes. All wire shall be terminated using the T568B wiring practices. All cable shall be Plenum rated.<br />

Cat 5e cable used <strong>for</strong> Voice/Data applications shall have a Blue jacket terminated on Black jacks in the<br />

MDF/IDF and Electrical Ivory at the desktop.<br />

Cat 5e cables used <strong>for</strong> wireless applications shall have a White jacket terminated White jacks in the<br />

MDF/IDF and RJ45 plugs at the field end.<br />

Cat 5e cables used <strong>for</strong> security applications shall have a Violet jacket and shall be terminated on Violet<br />

jacks in the MDF/IDF and Violet jacks at the field end.<br />

Cat 5e cables used <strong>for</strong> security applications shall have a Red jacket and terminated on Red jacket in the<br />

MDF/IDF and Red jacks at the field end.<br />

Cat 6 cables used <strong>for</strong> Voice/Data applications shall have a Yellow jacket and terminated on Yellow<br />

jacks in the MDF/IDF and Electrical Ivory at the desktop.<br />

Special colored or special use jacks at the customers request may be substituted at the field end with<br />

permission from the ITSD department.<br />

Walls are to be dropped and wires concealed where possible with jacks located at a standard 18”<br />

height.<br />

All cables shall be labeled on both ends and tested using a CAT 5e/6 certified test unit and results<br />

presented electronically to the ITSD department.<br />

All cable pulled through a conduit in a floor or underground application shall be Underground Rated.<br />