Technical Requirements<br />

Administrative Space<br />

BATHROOM W/SHOWER (ADA) (AS-12)<br />

ROOM FUNCTION<br />

This space will provide toilet and lavatory facilities <strong>for</strong> a child<br />

who is ill and under the supervision <strong>of</strong> the Nurse. A shower<br />

is also included to allow <strong>for</strong> children to be cleaned up, if<br />

necessary.<br />

TECHNICAL REQUIREMENTS<br />

ARCHITECTURAL<br />

Floor<br />

Resil. Flooring or Ceramic Tile<br />

Base<br />

Rubber<br />

Walls See Note 4<br />

Ceiling<br />

Acoustical Tile System<br />

Lighting<br />

Fluorescent<br />

ROOM DATA<br />

Net Square Feet (ASF) 60 asf<br />

Avg. No. <strong>of</strong> Occupants 1<br />

No. <strong>of</strong> Spaces by Type 1 (Eastside); 1 (Westside)<br />

<strong>SA</strong>MPLE ROOM LAYOUT<br />

This diagram is included as a planning tool to ensure that the space<br />

will function as the users require within the assigned square feet. It is<br />

not intended to dictate the final design or configuration <strong>of</strong> the space.<br />

MECHANICAL / PLUMBING<br />

Temperature/Humidity Variable 68°f to 75°f @ 50%rh<br />

Air Changes/Hour min. per Code<br />

Hot Water (HW) X Cold Water (CW) X<br />

Other See Notes 6 thru 9<br />

ELECTRICAL / COMMUNICATIONS<br />

Power 110v/20a/1-phase - See Note 11<br />

Dedicated Circuits<br />

Data<br />

Other<br />

Stand-by Power<br />

FURNISHINGS, FIXTURES & EQUIPMENT<br />

NOTES (CONTINUED)<br />

(1) Standard Flush Toilet (ADA) cfci 4. Install ceramic tile wainscot to 5’-0” aff at walls or to ceiling at<br />

(1) Lavatory (ADA) cfci<br />

perimeter walls and to ceiling in shower area. Install moistureresistant<br />

painted gypsum wallboard at all other wall locations<br />

(1) Walk-In Shower (ADA) cfci<br />

above tile and at ceiling.<br />

Wall-Mounted Mirror (At Lavatory)<br />

cfci 5. Provide direct lighting above shower stall. Install UL-rated fixture<br />

(1) Paper Towel Dispenser (Wall Mounted) cfci<br />

<strong>for</strong> wet locations.<br />

(1) Soap Dispenser (Wall Mounted) cfci 6. Provide exhaust fan to remove excess moisture from air.<br />

Exhaust to exterior.<br />

7. Provide plumbing <strong>for</strong> hot and cold water to sink and to shower.<br />

8. Provide floor drain in shower.<br />

9. Provide plumbing <strong>for</strong> flush toilet.<br />

NOTES<br />

10. All fixtures shall meet ADA requirements <strong>for</strong> accessibility.<br />

1. Reference “Code and Standards” chapter <strong>for</strong> in<strong>for</strong>mation<br />

regarding additional design requirements <strong>of</strong> this space which<br />

11. Convenience duplex GFCI power outlet shall be provided at<br />

may not be listed here.<br />

lavatory. When locating power outlets, pay special attention<br />

to the possible location <strong>of</strong> fixtures.<br />

2. Space will be adjacent to and accessible from the Sick/Isolation<br />

Area. Entry door to space shall be provided with keyed<br />

12. This space does not require natural light.<br />

lock.<br />

3. Utilize accessible shower pan or install non-slip ceramic tile<br />

floor at shower.<br />

Facility <strong>Programming</strong> and Consulting<br />

An Architectural Space Program <strong>for</strong> the <strong>City</strong> <strong>of</strong> <strong>San</strong> <strong>Antonio</strong><br />

Final - May 2013<br />

<strong>Pre</strong>-K 4 <strong>SA</strong> Early Childhood Centers - East and Westside Centers<br />

Page 4.25