12 Aqua 24 Aqua/Black Tracer 36 Aqua/Double Black Tracer<br />

11.5 Copper Cable Splicing<br />

Copper cable splicing is allowed only in backbone cable—never <strong>for</strong> horizontal cable which extends<br />

between the telecommunications room and the work area.<br />

Two common modular (groups <strong>of</strong> pairs) splicing techniques are in-line and foldback. Foldback<br />

splicing is the preferred method, where practicable.<br />

With the in-line splicing method, wire is placed in a straight-across arrangement and provides <strong>for</strong> little<br />

wire slack. <strong>The</strong> in-line method is not designed to be rearranged and should receive minimum handling.<br />

<strong>The</strong> foldback splicing method allows the conductors to be folded into the splice which in turn provides<br />

<strong>for</strong> maintenance, rearrangement, and transfer <strong>of</strong> the conductors. <strong>The</strong> foldback method typically<br />

requires more cable be stored within the splice and could increase the size <strong>of</strong> the needed splice closure.<br />

<strong>The</strong> splice connecting hardware shall be selected by the designer to meet the application requirements.<br />

Follow the equipment manufacturer’s installation guidelines.<br />

<strong>The</strong> installer should pay particular attention to:<br />

• Check cable shield <strong>for</strong> presence <strong>of</strong> unsafe voltages.<br />

• Bond cable shields across the splice be<strong>for</strong>e splicing.<br />

• Bond cable shields to ground.<br />

11.6 Optical Fiber Cable Splicing<br />

<strong>The</strong>re are two major categories <strong>of</strong> field-splicing methods <strong>for</strong> optical fibers—fusion and mechanical.<br />

Both single-fiber and multiple-fiber (typically 6- or 12-fibers) splicing methods are available.<br />

Only fibers with the same core and cladding dimensions and similar per<strong>for</strong>mance characteristics<br />

(bandwidth) shall be spliced (e.g., 50 μm core to 50 μm core; 2000 MHz/km to 2000 MHz/km).<br />

<strong>The</strong> splice hardware shall be selected by the designer to meet the application requirements. Follow the<br />

equipment manufacturer’s installation guidelines.<br />