8.4.7.1 Examination<br />

A. Field Measurements: Verify dimensions in areas <strong>of</strong> installation by field measurements<br />

be<strong>for</strong>e fabrication and indicate measurements on shop drawings. Coordinate fabrication<br />

schedule with construction progress to avoid delaying the work.<br />

B. Established Dimensions: Where field measurements cannot be made without delaying the<br />

work, establish dimensions and proceed with fabricating units without field measurements.<br />

Coordinate supports, adjacent construction, and fixture locations to ensure actual dimensions<br />

correspond to established dimensions.<br />

8.4.7.2 <strong>Pre</strong>paration<br />

A. Contractor’s on-site RCDD supervisor shall review, approve and stamp all shop drawings,<br />

coordination drawings and record drawings.<br />

B. Complete site preparation and soil compaction be<strong>for</strong>e trenching and driving ground rods <strong>for</strong><br />

underground grid.<br />

C. Verify exact location <strong>of</strong> stub-up points <strong>for</strong> grounding <strong>of</strong> equipment, fences and building or<br />

steel structures.<br />

D. Copper and copper alloy connections should be cleaned prior to connection.<br />

8.4.8 Installation<br />

8.4.8.1 General<br />

1. Bonding conductors shall be routed with minimum bends or changes in direction and should<br />

be made directly to the points being bonded.<br />

2. Bonding connections should be made by using:<br />

a. Compression copper lugs. Use listed hardware that has been laboratory tested to<br />

eliminate most field problems.<br />

b. Exothermic welding (see NEC Article 250) within the ground electrode system, <strong>for</strong><br />

parts <strong>of</strong> a grounding system that are subject to corrosion or that must carry high currents<br />

reliably, or <strong>for</strong> locations that require minimum maintenance.<br />

3. Drive rods vertically, leaving top 18 inches exposed above finished grade. Exothermic-weld<br />

below-grade grounding connections, except at ground rods. Install additional ground rods as<br />

required to pass resistance test.<br />

4. Make connections to dry surfaces only. Remove paint, rust, oxides, scales, grease and dirt<br />

from surfaces be<strong>for</strong>e making connection. <strong>San</strong>d clean a one square inch area, drill, tap, and bolt<br />

conductor and connector to sanded area. Ensure proper conductivity.<br />

5. <strong>The</strong> No. 3/0 AWG insulated ground wire weld ends shall have a minimum amount <strong>of</strong> wire<br />

exposure from the conduit to each weld and a minimum amount <strong>of</strong> insulation removed at weld.<br />