<strong>The</strong> following Heating, Ventilating and Air Conditioning (HVAC) standards shall be observed<br />

in all MDF/IDF rooms:<br />

<strong>The</strong> temperature <strong>of</strong> any MDF/IDF room should be maintained between 55° F and 78° F.<br />

<strong>The</strong> relative humidity <strong>of</strong> any MDF/IDF room should be maintained between 14% and 45%.<br />

5.5.2 Lighting Standards<br />

MDF/IDF rooms shall have sufficient lighting so that Maintenance and other personnel can<br />

easily see labels, equipment ports, and any other item <strong>of</strong> interest in the room including<br />

communications facilities. Lighting shall not be placed directly over cable trays.<br />

5.5.3 Interior Finishes<br />

Floors, walls, and ceilings shall be treated to eliminate dust. Finishes shall be light in color to<br />

enhance room lighting. Flooring materials having antistatic properties shall be selected. Sealed<br />

concrete or tiled floors are recommended. Carpet or rugs are not permitted in MDF/IDF rooms.<br />

Existing MDF/IDF rooms not in compliance with this requirement that contain electronics are<br />

to be reconditioned as soon as conditions allow.<br />

5.5.4 Electrical Power Standards<br />

<strong>The</strong> following electrical power standards should be observed in all communications rooms:<br />

<strong>The</strong> standard service is two dedicated 120 VAC, 60 Hz outlets protected by a 20A circuit<br />

breaker and should be located on the cable tray directly above the cabinet. In the event that the<br />

outlets cannot be mounted above the cabinet, the outlets should be mounted either directly<br />

behind a floor-mounted cabinet or directly below a wall-mounted cabinet approximately 18”<br />

from the floor. In addition, a dedicated 120 VAC, 60 Hz outlet protected by a 20A circuit<br />

breaker should be installed on the wall that is covered with plywood <strong>for</strong> service providers<br />

approximately 18” from the floor.<br />

Non-standard service is provided on a case-by-case basis to equipment requiring different<br />

service and require approval from the ITSD Communications Manager or his designated point<br />

<strong>of</strong> contact.<br />

At locations where a Terra Frame is installed at least one 208v 30 amp and onefour 208v 20<br />

Amp outlet with L6-20P should be located on the cable tray directly above the cabinet. In the<br />

event that the outlets cannot be installed above the cabinet, the outlets should be mounted on<br />

the wall directly behind the cabinet approximately 18” from the floor.<br />

Note: When the equipment in a particular rack exceeds the capacity <strong>of</strong> the existing service<br />

outlets or associated 20A circuit breaker, installing additional service outlets dedicated to a<br />

second 20A circuit breaker is permissible.<br />