6. <strong>The</strong> No. 6 AWG insulated ground wire connecting ends shall have a minimum amount <strong>of</strong><br />

insulation removed at ground lug.<br />

7. Do not connect ground wire in power cable assemblies to the communications ground<br />

system.<br />

8.4.8.2 TMGB<br />

1. Install the TMGB in the MDF as shown in the communications drawing set. <strong>The</strong> TMGB<br />

should be located so that the bonding conductor is as short and straight as possible. Maintain<br />

clearances required by applicable electrical codes.<br />

2. <strong>The</strong> TMGB shall be attached to the wall studs with tapping screws with the bottom <strong>of</strong> the<br />

busbar 84 inches above finished floor (AFF).<br />

3. <strong>The</strong> TMGB shall be <strong>of</strong>fset from the wall two inches and shall include support brackets and<br />

insulators.<br />

4. Connect the TMGB to the main building electrical entrance facility ground system and<br />

telecommunications primary protectors.<br />

5. TMGB Weld Requirements<br />

a. <strong>The</strong> No. 3/0 AWG ground wire weld from the main source shall not exceed one inch<br />

from one end <strong>of</strong> the TMGB busbar.<br />

b. One additional weld shall not exceed one inch from the opposite end <strong>of</strong> the TMGB<br />

busbar.<br />

c. Two or more additional welds shall not exceed the one-inch spacing from the welds<br />

toward the center <strong>of</strong> the busbar.<br />

d. <strong>The</strong> No. 3/0 AWG insulated ground wire weld ends shall have a minimum amount <strong>of</strong><br />

wire exposure from the conduit to the weld and a minimum amount <strong>of</strong> insulation removed<br />

at weld.<br />

8.4.8.3 TGB<br />

1. Install the TGBs in the IDFs. <strong>The</strong> TGB should also be located so that the bonding conductor<br />

is as short and straight as possible. Maintain clearances required by applicable electrical codes.<br />

2. <strong>The</strong> TGB shall be attached to the wall studs with tapping screws with the bottom <strong>of</strong> the<br />

busbar 84 inches above finished floor (AFF).<br />

3. <strong>The</strong> TGB shall be <strong>of</strong>fset from the wall two inches and shall include support brackets and<br />

insulators.<br />

4. TGB Weld Requirements<br />

a. <strong>The</strong> No. 3/0 AWG ground wire weld from the TMGB shall not exceed one inch from<br />

one end <strong>of</strong> the TGB busbar.<br />

b. One additional weld shall not exceed one inch from the opposite end <strong>of</strong> the TGB<br />

busbar.<br />