Modbus communication Data addresses and encoding<br />
PCRED301005EN - 06/<strong>20</strong>08<br />
Synchronization zone<br />
The synchronization zone is a table which contains the absolute date and time for<br />
the time-tagging function. Time messages should be written in a single block<br />
containing 4 words, using function 16: write word.<br />
Messages can be read word by word or by groups of words using function 3.<br />
Synchronization zone Word address Access Modbus function<br />
enabled<br />
Binary time (year) 0002 Read/write 3, 16<br />
Binary time (months + days) 0003 Read 3<br />
Binary time (hours + minutes) 0004 Read 3<br />
Binary time (milliseconds) 0005 Read 3<br />
See "time-tagging of events" chapter for data format.<br />
Identification zone<br />
The identification zone contains system-type information pertaining to the<br />
identification of the Sepam equipment.<br />
Some of the information in the identification zone is also found in the configuration<br />
zone at the address FC00h.<br />
Identification zone Word address Access Modbus function Format Value<br />
enabled<br />
Manufacturer identification 0006 R 3 0100<br />
Equipment 0007 R 3 0<br />
Marking + equipment type 0008 R 3 Idem FC01<br />
Modbus version 0009 R 3 Idem FC02<br />
Application version 000A/B R 3 Not managed 0<br />
Sepam check-word 000C R 3 Idem 0100<br />
Synthesis zone 000D R 3 Not managed 0<br />
Command 000E R/W 3/16 Not managed Init. to 0<br />
Extension address 000F R 3 FC00<br />
This zone is provided to ensure compatibility with existing equipment. A more complete description is available starting at address FC00h in the configuration zone<br />
or using the identification read function.<br />
First events zone<br />
The events zone is a table which contains a maximum of 4 time-tagged events.<br />
Events should be read in a single block containing 33 words using function 3.<br />
The exchange word can be written using functions 6 or 16, and read individually using<br />
function 3.<br />
Events zone 1 Word address Access Modbus function<br />
enabled<br />
Exchange word 0040 Read/write 3, 6, 16<br />
Event n°1 0041-0048 Read 3<br />
Event n°2 0049-0050 Read 3<br />
Event n°3 0051-0058 Read 3<br />
Event n°4 0059-0060 Read 3<br />
See "time-tagging of events" chapter for data format.<br />
Second events zone<br />
The events zone is a table which contains a maximum of 4 time-tagged events.<br />
Events should be read in a single block containing 33 words using function 3.<br />
The exchange word can be written using functions 6 or 16 and read individually using<br />
function 3.<br />
Events zone 2 Word address Access Modbus function<br />
enabled<br />
Exchange word 0070 Read/write 3, 6, 16<br />
Event n°1 0071-0078 Read 3<br />
Event n°2 0079-0080 Read 3<br />
Event n°3 0081-0088 Read 3<br />
Event n°4 0089-0090 Read 3<br />
See "time-tagging of events" chapter for data format.<br />