MT10252<br />

Network diagnosis<br />

functions<br />

tripping order<br />

T0<br />

PCRED301005EN - 06/<strong>20</strong>08<br />

I<br />

TRIP 1<br />

30 ms<br />

t<br />

Tripping current<br />

Negative sequence / unbalance<br />

Tripping current<br />

Operation<br />

This function gives the RMS value of currents at the prospective time of the last trip:<br />

b TRIP1: phase 1 current<br />

b TRIP2: phase 2 current<br />

b TRIP3: phase 3 current<br />

b TRIPI0: residual current.<br />

It is based on measurement of the fundamental component.<br />

This measurement is defined as the maximum RMS value measured during a 30 ms<br />

interval after the activation of the tripping contact on output O1.<br />

The tripping currents are saved in the event of a power failure.<br />

Readout<br />

The measurements may be accessed via:<br />

b the display of a Sepam with advanced UMI by pressing the key<br />

b the display of a PC with the SFT2841 software<br />

b the communication link.<br />

Characteristics<br />

Measurement range phase current 0.1 to 40 In (1)<br />

Residual current 0.1 to <strong>20</strong> In0 (1)<br />

Unit A or kA<br />

Accuracy ±5 % ±1 digit<br />

Display format 3 significant digits<br />

Resolution 0.1 A or 1 digit<br />

(1) In/In0 rated current set in the general settings.<br />

Negative sequence / unbalance<br />

Operation<br />

This function gives the negative sequence component: T = Ii/Ib<br />

The negative sequence current is determined based on the phase currents:<br />

b 3 phases<br />

1<br />

Ii -- I1 a<br />

3<br />

2 = × ( + I2 + aI3)<br />

with a<br />

j<br />

e<br />

b 2 phases<br />

2π<br />

=<br />

------<br />

3<br />

Ii<br />

1<br />

------ I1 a<br />

3<br />

2 = × – I3<br />

with a<br />

j<br />

e<br />

These 2 formulas are equivalent when there is no earth fault.<br />

2π<br />

=<br />

------<br />

3<br />

Readout<br />

The measurements may be accessed via:<br />

b the display of a Sepam with advanced UMI by pressing the key<br />

b the display of a PC with the SFT2841 software<br />

b the communication link.<br />

Characteristics<br />

Measurement range 10 to 500<br />

Unit % Ib<br />

Accuracy ±2 %<br />

Display format 3 significant digits<br />

Resolution 1 %<br />

Refresh interval 1 second (typical)<br />