Network diagnosis<br />
functions<br />
tripping order<br />
T0<br />
PCRED301005EN - 06/<strong>20</strong>08<br />
I<br />
TRIP 1<br />
30 ms<br />
t<br />
Tripping current<br />
Negative sequence / unbalance<br />
Tripping current<br />
Operation<br />
This function gives the RMS value of currents at the prospective time of the last trip:<br />
b TRIP1: phase 1 current<br />
b TRIP2: phase 2 current<br />
b TRIP3: phase 3 current<br />
b TRIPI0: residual current.<br />
It is based on measurement of the fundamental component.<br />
This measurement is defined as the maximum RMS value measured during a 30 ms<br />
interval after the activation of the tripping contact on output O1.<br />
The tripping currents are saved in the event of a power failure.<br />
Readout<br />
The measurements may be accessed via:<br />
b the display of a Sepam with advanced UMI by pressing the key<br />
b the display of a PC with the SFT2841 software<br />
b the communication link.<br />
Characteristics<br />
Measurement range phase current 0.1 to 40 In (1)<br />
Residual current 0.1 to <strong>20</strong> In0 (1)<br />
Unit A or kA<br />
Accuracy ±5 % ±1 digit<br />
Display format 3 significant digits<br />
Resolution 0.1 A or 1 digit<br />
(1) In/In0 rated current set in the general settings.<br />
Negative sequence / unbalance<br />
Operation<br />
This function gives the negative sequence component: T = Ii/Ib<br />
The negative sequence current is determined based on the phase currents:<br />
b 3 phases<br />
1<br />
Ii -- I1 a<br />
3<br />
2 = × ( + I2 + aI3)<br />
with a<br />
j<br />
e<br />
b 2 phases<br />
2π<br />
=<br />
------<br />
3<br />
Ii<br />
1<br />
------ I1 a<br />
3<br />
2 = × – I3<br />
with a<br />
j<br />
e<br />
These 2 formulas are equivalent when there is no earth fault.<br />
2π<br />
=<br />
------<br />
3<br />
Readout<br />
The measurements may be accessed via:<br />
b the display of a Sepam with advanced UMI by pressing the key<br />
b the display of a PC with the SFT2841 software<br />
b the communication link.<br />
Characteristics<br />
Measurement range 10 to 500<br />
Unit % Ib<br />
Accuracy ±2 %<br />
Display format 3 significant digits<br />
Resolution 1 %<br />
Refresh interval 1 second (typical)<br />