Protection functions Neutral voltage displacement<br />

ANSI code 59N<br />

PCRED301005EN - 06/<strong>20</strong>08<br />

Operation<br />

The protection function picks up if the residual voltage V0 is above a Vs0 set point,<br />

with V0 =<br />

V1 + V2 + V3 ,<br />

b it includes a definite time delay T<br />

b the residual voltage is either calculated from the 3 phase voltages or measured by<br />

an external VT.<br />

DE50249<br />

Block diagram<br />

Characteristics<br />

Vs0 set point<br />

Setting 2 % Unp to 80 % Unp if Vns0 (2) = sum of 3Vs<br />

2 % Unp to 80 % Unp if Vns0 (2) = Uns/3<br />

5 % Unp to 80 % Unp if Vns0 (2) = Uns/3<br />

Accuracy (1) ±2 % or ±0.005 Unp<br />

Resolution 1 %<br />

Drop-out/pick-up ratio 97 % ±1 %<br />

Time delay T<br />

Setting 50 ms to 300 s<br />

Accuracy (1) ±2 %, or ±25 ms<br />

Resolution 10 ms or 1 digit<br />

Characteristic times<br />

Operation time pick-up < 55 ms<br />

Overshoot time < 35 ms<br />

Reset time < 55 ms<br />

(1) In reference conditions (IEC 60255-6).<br />

(2) Vns0 is one of the general settings.<br />

3/29<br />