Control and monitoring<br />

functions<br />

PCRED301005EN - 06/<strong>20</strong>08<br />

DE51139<br />

Disturbance recording triggering<br />

Description<br />

The recording of analog and logic signals may be triggered by different events,<br />

according to control matrix parameter setting or by <strong>manual</strong> action:<br />

b triggering by the grouping of all pick-up signals of the protection functions in<br />

service<br />

b triggering by the delayed outputs of selected protection functions<br />

b triggering by selected logic inputs<br />

b <strong>manual</strong> triggering by a remote control order (TC10)<br />

b <strong>manual</strong> triggering via the SFT2841 software tool.<br />

Disturbance recording may be:<br />

b inhibited via the SFT2841 software or by remote control order (TC8)<br />

b validated via the SFT2841 software or by remote control order (TC9).<br />

Block diagram<br />

TS/TC equivalence for each protocol<br />

Modbus DNP3 IEC 60870-5-103 IEC 61850<br />

TC Binary Output ASDU, FUN, INF LN.DO.DA<br />

TC8 BO03 - RDRE1.RcdInh.ctlVal<br />

TC9 BO04 - RDRE1.RcdInh.ctlVal<br />

TC10 BO04 - RDRE1.RcdTrg.ctlVal<br />

4/11<br />