Protection functions General<br />

Tripping curves<br />

Example.<br />

Detection of restriking faults with adjustable timer hold.<br />

Timer hold dependent on current I. Constant timer hold.<br />

3/38<br />

Setting of IDMT tripping curves, time delay T or TMS factor<br />

The time delays of current IDMT tripping curves (except for customized and RI<br />

curves) may be set as follows:<br />

b time T, operating time at 10 x Is<br />

b TMS factor, factor shown as T/β in the equations on the left.<br />

13.5<br />

Example: tI () --------------<br />

T<br />

= × TMS where TMS = ------- .<br />

I<br />

---- – 1<br />

1.5<br />

Is<br />

The IEC curve of the VIT type is positioned so as to be the same with<br />

TMS = 1 or T = 1.5 s.<br />

Timer hold<br />

The adjustable timer hold T1 is used for:<br />

b detection of restriking faults (DT curve)<br />

b coordination with electromechanical relays (IDMT curve).<br />

b Timer hold may be inhibited if necessary.<br />

Equation for IDMT timer hold curve<br />

T1<br />

Equation: t where .<br />

r<br />

() I<br />

1 ⎛ I<br />

---- ⎞<br />

⎝Is⎠ T1 = timer hold setting (timer hold for I reset = 0 and TMS = 1)<br />

T = tripping time delay setting (at 10 Is)<br />

b = basic tripping curve value at .<br />

2<br />

----------------------<br />

–<br />

T T<br />

= × -- -- = T M S<br />

β β<br />

k<br />

10 α -----------------<br />

– 1<br />

DE50754<br />

PCRED301005EN - 06/<strong>20</strong>08