Protection functions General<br />
Tripping curves<br />
Example.<br />
Detection of restriking faults with adjustable timer hold.<br />
Timer hold dependent on current I. Constant timer hold.<br />
3/38<br />
Setting of IDMT tripping curves, time delay T or TMS factor<br />
The time delays of current IDMT tripping curves (except for customized and RI<br />
curves) may be set as follows:<br />
b time T, operating time at 10 x Is<br />
b TMS factor, factor shown as T/β in the equations on the left.<br />
13.5<br />
Example: tI () --------------<br />
T<br />
= × TMS where TMS = ------- .<br />
I<br />
---- – 1<br />
1.5<br />
Is<br />
The IEC curve of the VIT type is positioned so as to be the same with<br />
TMS = 1 or T = 1.5 s.<br />
Timer hold<br />
The adjustable timer hold T1 is used for:<br />
b detection of restriking faults (DT curve)<br />
b coordination with electromechanical relays (IDMT curve).<br />
b Timer hold may be inhibited if necessary.<br />
Equation for IDMT timer hold curve<br />
T1<br />
Equation: t where .<br />
r<br />
() I<br />
1 ⎛ I<br />
---- ⎞<br />
⎝Is⎠ T1 = timer hold setting (timer hold for I reset = 0 and TMS = 1)<br />
T = tripping time delay setting (at 10 Is)<br />
b = basic tripping curve value at .<br />
2<br />
----------------------<br />
–<br />
T T<br />
= × -- -- = T M S<br />
β β<br />
k<br />
10 α -----------------<br />
– 1<br />
DE50754<br />
PCRED301005EN - 06/<strong>20</strong>08