Switchgear diagnosis<br />

functions<br />

PCRED301005EN - 06/<strong>20</strong>08<br />

Cumulative breaking current and<br />

number of operations<br />

Cumulative breaking current<br />

Operation<br />

This function indicates the cumulative breaking current in square kiloamperes (kA) 2<br />

for five current ranges.<br />

It is based on measurement of the fundamental component.<br />

The current ranges displayed are:<br />

b 0 < I < 2 In<br />

b 2 In < I < 5 In<br />

b 5 In < I < 10 In<br />

b 10 In < I < 40 In<br />

b I > 40 In.<br />

The function also provides the total number of operations and the cumulative total of<br />

breaking current in (kA)².<br />

Each value is saved in the event of a power failure.<br />

Refer to switchgear documentation for use of this information.<br />

Number of operation<br />

The function is activated by tripping commands (O1 relay).<br />

This value is saved in the event of a power failure.<br />

Readout<br />

The measurements may be accessed via:<br />

b the display of a Sepam with advanced UMI by pressing the key<br />

b the display of a PC with the SFT2841 software<br />

b the communication link.<br />

The initial values may be introduced using the SFT2841 software tool to take into<br />

account the real state of a used breaking device.<br />

Characteristics<br />

Breaking current (kA) 2<br />

Range 0 to 65535 (kA) 2<br />

Unit primary (kA) 2<br />

Accuracy (1) ±10 %<br />

Number of operations<br />

Range 0 to 65535<br />

(1) At In, in reference conditions (IEC 60255-6).<br />

2/15<br />