sepam 20 user manual - Schneider Electric
sepam 20 user manual - Schneider Electric
sepam 20 user manual - Schneider Electric
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
4<br />
Control and monitoring<br />
functions<br />
4/4<br />
Assignment of logic<br />
inputs / outputs<br />
The use of the preset control and monitoring functions requires exclusive parameter<br />
setting and particular wiring of the inputs according to their application and the type<br />
of Sepam.<br />
The advanced UMI or the SFT2841 software may be used to assign inputs and set<br />
the control and monitoring function parameters.<br />
Since an input may only be assigned to a single function, not all the functions are<br />
available at the same time.<br />
Example: if the logic discrimination function is used, the switching of groups of<br />
settings function may not be used.<br />
Table of input/output assignment by application<br />
Functions<br />
Logic inputs<br />
S<strong>20</strong> S23 T<strong>20</strong> T23 M<strong>20</strong> B21 - B22 Assignment<br />
Open position b b b b b b I11<br />
Closed position b b b b b b I12<br />
Logic discrimination, receive blocking input<br />
b b b b I13<br />
Switching of groups of settings A/B<br />
b b b b b<br />
External reset<br />
External tripping 4 (1)<br />
b b b b b b<br />
I14<br />
b b b b b b<br />
External tripping 1 (1)<br />
b b b<br />
External network synchronization<br />
b b<br />
(2) b<br />
b<br />
(2) b b<br />
I21<br />
b b b<br />
External tripping 2 (1)<br />
b b b<br />
Motor re-acceleration<br />
(3) b (3) b b I22<br />
b<br />
External tripping 3 (1)<br />
Buchholz alarm (1) (Buchholz alarm message)<br />
Rotor rotation detection<br />
Thermistor tripping (1)<br />
Inhibit earth fault protection<br />
End of charging position<br />
Thermostat alarm (1) (thermostat alarm message)<br />
Thermistor alarm (1)<br />
External tripping 5 and 50BF activation (1)<br />
Inhibit remote control, excluding TC1 (1)<br />
Inhibit remote control, including TC1 (1)<br />
SF6-1<br />
SF6-2<br />
Change of thermal settings<br />
Inhibit thermal overload<br />
Inhibit recloser<br />
b b<br />
b<br />
b b<br />
b<br />
b<br />
b<br />
b<br />
b<br />
b (1)<br />
b<br />
b<br />
b<br />
b<br />
b<br />
b (4)<br />
b<br />
b<br />
b<br />
b<br />
b<br />
b<br />
b<br />
b<br />
b<br />
b<br />
b<br />
b (4)<br />
b<br />
b<br />
b<br />
b<br />
b<br />
b (1)<br />
b<br />
b<br />
b<br />
b<br />
b<br />
b<br />
b<br />
b<br />
b<br />
b<br />
b<br />
b<br />
b<br />
b<br />
b<br />
b<br />
b<br />
b I23<br />
I24<br />
b<br />
I25<br />
b<br />
b<br />
b I26<br />
Logic outputs<br />
Tripping b b b b b b O1<br />
Inhibit closing b b b b b b O2<br />
Watchdog b b b b b b O4<br />
Close order b b b b b b O11<br />
Note: all of the logic inputs are available via the communication link and are accessible in the SFT2841 control matrix for other non predefined applications.<br />
(1) These inputs have parameter setting with the prefix "NEG" for undervoltage type operation.<br />
(2) Buchholz/Gas trip message.<br />
(3) Thermostat trip message.<br />
(4) Pressure trip message.<br />
PCRED301005EN - 06/<strong>20</strong>08