6<br />

PE50024<br />

Installation ACE937<br />

Fiber optic interface<br />

6/42<br />

Function<br />

The ACE937 interface is used to connect Sepam to a fiber optic communication star<br />

system.<br />

This remote module is connected to the Sepam base unit by a CCA612 cord.<br />

Characteristics<br />

ACE937 module<br />

Weight 0.1 kg (0.22 lb)<br />

Assembly On symmetrical DIN rail<br />

Power supply Supplied by Sepam<br />

ACE937 fiber optic connection interface. Operating temperature -25°C to +70°C (-13°F to +158°F)<br />

Environmental characteristics<br />

Fiber optic interface<br />

Same characteristics as Sepam base units<br />

Fiber type Graded-index multimode silica<br />

Wavelength 8<strong>20</strong> nm (invisible infra-red)<br />

Type of connector ST (BFOC bayonet fiber optic connector)<br />

CAUTION<br />

HAZARD OF BLINDING<br />

Never look directly into the end of the fiber optic.<br />

Failure to follow this instruction can cause<br />

serious injury.<br />

Fiber optic<br />

diameter (µm)<br />

50/125<br />

62.5/125<br />

100/140<br />

Numerical<br />

aperture (NA)<br />

0.2<br />

0.275<br />

0.3<br />

Maximum Minimum optical<br />

attenuation power available<br />

(dBm/km) (dBm)<br />

2.7 5.6<br />

3.2 9.4<br />

4 14.9<br />

Maximum<br />

fiber length<br />

700 m (2300 ft)<br />

1800 m (5900 ft)<br />

2800 m (9<strong>20</strong>0 ft)<br />

<strong>20</strong>0 (HCS) 0.37 6 19.2 2600 m (8500 ft)<br />

DE80037<br />

DE51666<br />

mm<br />

in<br />

1.81<br />

2.83<br />

3.46<br />

(1) 70 mm (2.8 in) with CCA612 cord connected.<br />

Maximum length calculated with:<br />

b Minimum optical power available<br />

b Maximum fiber attenuation<br />

b Losses in 2 ST connectors: 0.6 dBm<br />

b Optical power margin: 3 dBm (according to IEC 60870 standard).<br />

Example for a 62.5/125 µm fiber<br />

Lmax = (9.4 - 3 - 0.6)/3.2 = 1.8 km (1.12 mi)<br />

Description and dimensions<br />

C<br />

RJ45 socket to connect the interface to the base unit with a CCA612 cord.<br />

1 Link activity LED, flashes when communication is active<br />

(sending or receiving in progress).<br />

2 Rx, female ST type connector (Sepam receiving).<br />

3 Tx, female ST type connector (Sepam sending).<br />

Connection<br />

b The sending and receiving fiber optic fibers must be equipped with male ST type<br />

connectors<br />

b Fiber optics screw-locked to Rx and Tx connectors.<br />

The interface is to be connected to connector<br />

cord (length = 3 m or 9.8 ft, green fittings).<br />

C<br />

on the base unit using a CCA612<br />