PE50021<br />
DE80121<br />
Installation MET148-2<br />
Temperature sensor module<br />
1.81<br />
mm<br />
in<br />
5.67<br />
(1) 70 mm (2.8 in) with CCA77x cord connected.<br />
PCRED301005EN - 06/<strong>20</strong>08<br />
3.46<br />
Function<br />
The MET148-2 module can be used to connect 8 temperature sensors (RTDs)<br />
of the same type:<br />
b Pt100, Ni100 or Ni1<strong>20</strong> type RTDs, according to parameter setting<br />
b 3-wire temperature sensors<br />
b A single module for each Sepam series <strong>20</strong> base unit, to be connected by one of<br />
the CCA770 (0.6 or 2 ft), CCA772 (2 m or 6.6 ft) or<br />
CCA774 (4 m or 13.1 ft) cords<br />
b 2 modules for each Sepam series 40 or series 80 base unit, to be connected by<br />
CCA770 (0.6 or 2 ft), CCA772 (2 m or 6.6 ft) or CCA774 (4 m or 13.1 ft) cords<br />
The temperature measurement (e.g. in a transformer or motor winding) is<br />
utilized by the following protection functions:<br />
b Thermal overload (to take ambient temperature into account)<br />
b Temperature monitoring.<br />
Characteristics<br />
MET148-2 module<br />
Weight 0.2 kg (0.441 lb)<br />
Assembly On symmetrical DIN rail<br />
Operating temperature -25°C to +70°C (-13°F to +158°F)<br />
Environmental characteristics Same characteristics as Sepam base units<br />
Temperature sensors Pt100 Ni100/Ni1<strong>20</strong><br />
Isolation from earth None None<br />
Current injected in RTD 4 mA 4 mA<br />
Description and dimensions<br />
A Terminal block for RTDs 1 to 4<br />
B Terminal block for RTDs 5 to 8<br />
Da RJ45 connector to connect the module to the base unit with a CCA77x cord<br />
Dd RJ45 connector to link up the next remote module with a CCA77x cord<br />
(according to application)<br />
t Grounding/earthing terminal<br />
1 Jumper for impedance matching with load resistor (Rc),<br />
to be set to:<br />
b Rc,<br />
if the module is not the last interlinked module (default position)<br />
b Rc, if the module is the last interlinked module.<br />
2 Jumper used to select module number, to be set to:<br />
b MET1: 1st MET148-2 module, to measure temperatures T1 to T8<br />
(default position)<br />
b MET2: 2nd MET148-2 module, to measure temperatures T9 to T16<br />
(for Sepam series 40 and series 80 only).<br />
6/33<br />
6