PE50021<br />

DE80121<br />

Installation MET148-2<br />

Temperature sensor module<br />

1.81<br />

mm<br />

in<br />

5.67<br />

(1) 70 mm (2.8 in) with CCA77x cord connected.<br />

PCRED301005EN - 06/<strong>20</strong>08<br />

3.46<br />

Function<br />

The MET148-2 module can be used to connect 8 temperature sensors (RTDs)<br />

of the same type:<br />

b Pt100, Ni100 or Ni1<strong>20</strong> type RTDs, according to parameter setting<br />

b 3-wire temperature sensors<br />

b A single module for each Sepam series <strong>20</strong> base unit, to be connected by one of<br />

the CCA770 (0.6 or 2 ft), CCA772 (2 m or 6.6 ft) or<br />

CCA774 (4 m or 13.1 ft) cords<br />

b 2 modules for each Sepam series 40 or series 80 base unit, to be connected by<br />

CCA770 (0.6 or 2 ft), CCA772 (2 m or 6.6 ft) or CCA774 (4 m or 13.1 ft) cords<br />

The temperature measurement (e.g. in a transformer or motor winding) is<br />

utilized by the following protection functions:<br />

b Thermal overload (to take ambient temperature into account)<br />

b Temperature monitoring.<br />

Characteristics<br />

MET148-2 module<br />

Weight 0.2 kg (0.441 lb)<br />

Assembly On symmetrical DIN rail<br />

Operating temperature -25°C to +70°C (-13°F to +158°F)<br />

Environmental characteristics Same characteristics as Sepam base units<br />

Temperature sensors Pt100 Ni100/Ni1<strong>20</strong><br />

Isolation from earth None None<br />

Current injected in RTD 4 mA 4 mA<br />

Description and dimensions<br />

A Terminal block for RTDs 1 to 4<br />

B Terminal block for RTDs 5 to 8<br />

Da RJ45 connector to connect the module to the base unit with a CCA77x cord<br />

Dd RJ45 connector to link up the next remote module with a CCA77x cord<br />

(according to application)<br />

t Grounding/earthing terminal<br />

1 Jumper for impedance matching with load resistor (Rc),<br />

to be set to:<br />

b Rc,<br />

if the module is not the last interlinked module (default position)<br />

b Rc, if the module is the last interlinked module.<br />

2 Jumper used to select module number, to be set to:<br />

b MET1: 1st MET148-2 module, to measure temperatures T1 to T8<br />

(default position)<br />

b MET2: 2nd MET148-2 module, to measure temperatures T9 to T16<br />

(for Sepam series 40 and series 80 only).<br />

6/33<br />