Protection functions Setting ranges<br />

Functions Settings Time delays<br />

ANSI 50N/51N or 50G/51G - Earth fault / Sensitive earth fault<br />

Tripping time delay Timer hold<br />

Tripping curve Definite time DT<br />

SIT, LTI, VIT, EIT, UIT (1) DT<br />

RI DT<br />

IEC: SIT/A,LTI/B, VIT/B, EIT/C DT or IDMT<br />

IEEE: MI (D), VI (E), EI (F) DT or IDMT<br />

IAC: I, VI, EI DT or IDMT<br />

Is0 set point 0.1 to 15 In0 Definite time Inst ; 0.05 s to 300 s<br />

0.1 to 1 In0 IDMT 0.1 s to 12.5 s at 10 Is0<br />

Timer hold Definite time (DT ; timer hold) Inst ; 0.05 s to 300 s<br />

IDMT (IDMT ; reset time) 0.5 s to <strong>20</strong> s<br />

ANSI 59 - Overvoltage phase-to-phase<br />

50 to 150 % of Unp 0.05 s to 300 s<br />

ANSI 59N - Neutral voltage displacement<br />

2 to 80 % of Unp 0.05 s to 300 s<br />

ANSI 66 - Starts per hour<br />

Starts per period 1 to 60 Period 1 to 6 hr<br />

Consecutive starts 1 to 60 Time between starts 0 to 90 mn<br />

ANSI 81H - Overfrequency<br />

50 to 53 Hz or 60 to 63 Hz 0.1 s to 300 s<br />

ANSI 81L - Underfrequency<br />

45 to 50 Hz or 55 to 60 Hz 0.1 s to 300 s<br />

ANSI 81R - Rate of change of frequency<br />

0.1 to 10 Hz/s Inst ; 0.15 s to 300 s<br />

(1) Tripping as of 1.2 Is.<br />