Modbus communication Configuring the communication<br />
interfaces<br />
SFT2841: Sepam Configuration screen.<br />
SFT2841: communication configuration window for ACE949.<br />
5/4<br />
Access to configuration parameters<br />
The Sepam communication interfaces are configured using SFT2841 software.<br />
The configuration parameters can be accessed from the Communication<br />
configuration window in SFT2841.<br />
To access this window:<br />
b open the Sepam configuration window in SFT2841<br />
b check the box for ACE9xx (communication interface)<br />
b click : the Communication configuration window appears<br />
b select the type of interface used: ACE949/ACE959/ACE937, ACE969TP or<br />
ACE969FO<br />
b select the Modbus communication protocol.<br />
The configuration parameters will vary depending on the communication interface<br />
selected: ACE949/ACE959/ACE937, ACE969TP or ACE969FO. The table below<br />
specifies the parameters to be configured depending on the communication interface<br />
chosen.<br />
Parameters to be configured ACE949<br />
ACE959<br />
ACE937<br />
ACE969TP ACE969FO<br />
Physical layer parameters b b b<br />
Fiber-optic parameters b<br />
Modbus advanced parameters b b b<br />
E-LAN parameters b b<br />
Configuring the physical layer of the Modbus port<br />
Asynchronous serial transmission is used with the following character format:<br />
b 8 data bits<br />
b 1 stop bit<br />
b parity according to parameter setting.<br />
The number of stop bits is always fixed at 1.<br />
If a configuration with Parity has been selected, each character will contain 11 bits<br />
(1 start bit + 8 data bits + 1parity bit + 1 stop bit)<br />
If a No Parity configuration has been selected, each character will contain 10 bits<br />
(1 start bit + 8 data bits + 1 stop bit).<br />
The configuration parameters for the physical layer of the Modbus port are:<br />
b slave number (Sepam address)<br />
b transmission speed<br />
b parity check type.<br />
Parameters Authorized values Default value<br />
Sepam address 1 to 247 1<br />
Speed 4800, 9600, 19<strong>20</strong>0 or<br />
38400 bauds<br />
19<strong>20</strong>0 bauds<br />
Parity None, Even or Odd Even<br />
Configuring the ACE969FO-2 fiber-optic port<br />
The configuration for the physical layer of the ACE969FO-2 fiber-optic port is<br />
completed with the following 2 parameters:<br />
b link idle state: light-on or light-off<br />
b echo mode: with or without.<br />
Fiber-optic parameters Authorized values Default value<br />
Link idle state Light Off or Light On Light Off<br />
Echo mode Yes (fiber-optic ring)<br />
or No (fiber-optic star)<br />
No<br />
Note: in echo mode, the Modbus master will receive the echo of its own request before the<br />
slave's reply. The Modbus master must be able to disregard this echo. Otherwise, it is impossible<br />
to create a Modbus fiber-optic ring.<br />