DE80231<br />

DE80231<br />

Installation CSH1<strong>20</strong> and CSH<strong>20</strong>0<br />

Core balance CTs<br />

PCRED301005EN - 06/<strong>20</strong>08<br />

DANGER<br />

HAZARD OF ELECTRIC SHOCK, ELECTRIC<br />

ARC OR BURNS<br />

b Only qualified personnel should install this<br />

equipment. Such work should be performed only<br />

after reading this entire set of instructions and<br />

checking the technical characteristics of the<br />

device.<br />

b NEVER work alone.<br />

b Turn off all power supplying this equipment<br />

before working on or inside it. Consider all<br />

sources of power, including the possibility of<br />

backfeeding.<br />

b Always use a properly rated voltage sensing<br />

device to confirm that all power is off.<br />

b Only CSH1<strong>20</strong>, CSH<strong>20</strong>0 and CSH280 core<br />

balance CTs can be used for direct residual<br />

current measurement. Other residual current<br />

sensors require the use of an intermediate<br />

device, CSH30, ACE990 or CCA634.<br />

b Install the core balance CTs on insulated<br />

cables.<br />

b Cables with a rated voltage of more than<br />

1000 V must also have an earthed shielding.<br />

Failure to follow these instructions will result<br />

in death or serious injury.<br />

E40465<br />

Assembly<br />

Group the MV cable (or cables) in the<br />

middle of the core balance CT.<br />

Use non-conductive binding to hold the<br />

cables.<br />

Remember to insert the 3 medium voltage<br />

cable shielding earthing cables<br />

through the core balance CT.<br />

CAUTION Connection<br />

HAZARD OF NON-OPERATION<br />

Do not connect the secondary circuit of the CSH<br />

core balance CTs to earth.<br />

This connection is made in Sepam.<br />

Failure to follow this instruction can cause<br />

Sepam to operate incorrectly.<br />

Assembly on MV cables. Assembly on mounting<br />

plate.<br />

E40466<br />

Connection to Sepam series <strong>20</strong> and Sepam series 40<br />

To residual current I0 input, on connector A , terminals 19 and 18 (shielding).<br />

Connection to Sepam series 80<br />

b To residual current I0 input, on connector E , terminals 15 and 14 (shielding)<br />

b To residual current I'0 input, on connector E<br />

, terminals 18 and 17 (shielding).<br />

Recommended cable<br />

b Sheathed cable, shielded by tinned copper braid<br />

b Minimum cable cross-section 0.93 mm² (AWG 18)<br />

b Resistance per unit length < 100 mΩ/m (30.5 mΩ/ft)<br />

b Minimum dielectric strength: 1000 V (700 Vrms)<br />

b Connect the cable shielding in the shortest manner possible to Sepam<br />

b Flatten the connection cable against the metal frames of the cubicle.<br />

The connection cable shielding is grounded in Sepam. Do not ground the cable by<br />

any other means.<br />

The maximum resistance of the Sepam connection wiring must not exceed 4 Ω<br />

(i.e. <strong>20</strong> m maximum for 100 mΩ/m or 66 ft maximum for 30.5 mΩ/ft).<br />

Connecting 2 CSH<strong>20</strong>0 CTs in parallel<br />

It is possible to connect 2 CSH<strong>20</strong>0 CTs in parallel if the cables will not fit through a<br />

single CT, by following the instructions below:<br />

b Fit one CT per set of cables.<br />

b Make sure the wiring polarity is correct.<br />

The maximum permissible current at the primary is limited to 6 kA - 1 s for all cables.<br />

DE51678<br />

6/23<br />

6