6<br />

Installation Base unit<br />

Connection of current inputs<br />

6/10<br />

DE51144<br />

Types S<strong>20</strong>/S23/T<strong>20</strong>/T23/M<strong>20</strong><br />

Connection to 1 A/5 A current sensors<br />

Connector Type Ref. Cable<br />

A Screw-type CCA6<strong>20</strong> b 1 wire 0.2 to 2.5 mm 2 (AWG 24-12)<br />

b 2 wires 0.2 to 1 mm 2 (AWG 24-18)<br />

Ring lug 6.35 mm<br />

(1/4 in)<br />

B Ring lug 4 mm<br />

(0.16 in)<br />

CCA622 b Cross-section: 0.2 to 2.5 mm 2 (AWG 24-12)<br />

b Stripped length: 6 mm (0.236 in)<br />

b Tightening torque: 0.7 to 1 N.m (6 to 9 lb-in)<br />

CCA630/<br />

CCA634<br />

b Cross-section: 1.5 to 6 mm 2 (AWG 16-10)<br />

b Stripped length: 6 mm (0.236 in)<br />

b Tightening torque: 1.2 N.m (11 lb-in)<br />

C RJ45 CCA612<br />

D RJ45 b CCA770: L = 0.6 m (2 ft)<br />

b CCA772: L = 2 m (6.6 ft)<br />

b CCA774: L = 4 m (13 ft)<br />

PCRED301005EN - 06/<strong>20</strong>08

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!