Metering functions Average current and peak<br />

demand currents<br />

PCRED301005EN - 06/<strong>20</strong>08<br />

Operation<br />

This function gives:<br />

b the average RMS current for each phase that has been obtained for each<br />

integration interval<br />

b the greatest average RMS current value for each phase that has been obtained<br />

since the last reset.<br />

The values are refreshed after each "integration interval", an interval that may be set<br />

from 5 to 60 mn.<br />

Readout<br />

The measurements may be accessed via:<br />

b the display of a Sepam with advanced UMI by pressing the key<br />

b the display of a PC with the SFT2841 software<br />

b the communication link.<br />

Resetting to zero:<br />

clear<br />

b press the key on the display when a peak demand current is displayed<br />

b via the clear command in the SFT2841 software<br />

b via the communication link (remote control order TC6).<br />

Characteristics<br />

Measurement range 0.1 to 1.5 In (1)<br />

Unit A or kA<br />

Accuracy typically ±1 % (2)<br />

±2 % from 0.3 to 1.5 In<br />

±5 % if < 0.3 In<br />

Display format (3) 3 significant digits<br />

Resolution 0.1 A or 1 digit<br />

Integration interval 5, 10, 15, 30, 60 minutes<br />

(1) In rated current set in the general settings.<br />

(2) at In, in reference conditions (IEC 60255-6).<br />

(3) Display of values: 0.02 to 40 In.<br />

TS/TC equivalence for each protocol<br />

Modbus DNP3 IEC 60870-5-103 IEC 61850<br />

TC Binary Output ASDU, FUN, INF LN.DO.DA<br />

TC6 BO12 - MSTA.RsMax.ctlVal<br />

2/5<br />

2