Modbus communication Data addresses and encoding<br />

PCRED301005EN - 06/<strong>20</strong>08<br />

Address word 0103: TS33 to TS48 (bit address 1030 to 103F)<br />

TS Use S<strong>20</strong> S23 T<strong>20</strong> T23 M<strong>20</strong> B21 B22<br />

33 Protection 50BF b b<br />

34 Recloser in service b b<br />

35 Recloser in progress b b<br />

36 Recloser permanent trip b b<br />

37 Recloser successful trip b b<br />

38 Send blocking input b b b b b<br />

39 Remote setting inhibited b b b b b b b<br />

40 Remote control inhibited b b b b b b b<br />

41 Sepam not reset after fault b b b b b b b<br />

42 Remote control/position discrepancy b b b b b b b<br />

43 Matching fault<br />

or Trip Circuit Supervision<br />

b b b b b b b<br />

44 Disturbance recording memorized b b b b b b b<br />

45 Control fault b b b b b b b<br />

46 Disturbance recording inhibited b b b b b b b<br />

47 Thermal protection inhibited b b b<br />

48 RTD fault b b b<br />

Address word 0104: TS49 to TS64 (bit address 1040 to 104F)<br />

TS Use S<strong>20</strong> S23 T<strong>20</strong> T23 M<strong>20</strong> B21 B22<br />

49 Protection 38/49T alarm set point sensor 1 b b b<br />

50 Protection 38/49T tripping set point sensor 1 b b b<br />

51 Protection 38/49T alarm set point sensor 2 b b b<br />

52 Protection 38/49T tripping set point sensor 2 b b b<br />

53 Protection 38/49T alarm set point sensor 3 b b b<br />

54 Protection 38/49T tripping set point sensor 3 b b b<br />

55 Protection 38/49T alarm set point sensor 4 b b b<br />

56 Protection 38/49T tripping set point sensor 4 b b b<br />

57 Protection 38/49T alarm set point sensor 5 b b b<br />

58 Protection 38/49T tripping set point sensor 5 b b b<br />

59 Protection 38/49T alarm set point sensor 6 b b b<br />

60 Protection 38/49T tripping set point sensor 6 b b b<br />

61 Protection 38/49T alarm set point sensor 7 b b b<br />

62 Protection 38/49T tripping set point sensor 7 b b b<br />

63 Protection 38/49T alarm set point sensor 8 b b b<br />

64 Protection 38/49T tripping set point sensor 8 b b b<br />

Address check-word 0100: bit 4 (bit address 1004)<br />

Use S<strong>20</strong> S23 T<strong>20</strong> T23 M<strong>20</strong> B21 B22<br />

Bit 4 Tripping by protection function b b b b b b b<br />