sepam 20 user manual - Schneider Electric
sepam 20 user manual - Schneider Electric
sepam 20 user manual - Schneider Electric
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Modbus communication Data addresses and encoding<br />
PCRED301005EN - 06/<strong>20</strong>08<br />
Address word 0103: TS33 to TS48 (bit address 1030 to 103F)<br />
TS Use S<strong>20</strong> S23 T<strong>20</strong> T23 M<strong>20</strong> B21 B22<br />
33 Protection 50BF b b<br />
34 Recloser in service b b<br />
35 Recloser in progress b b<br />
36 Recloser permanent trip b b<br />
37 Recloser successful trip b b<br />
38 Send blocking input b b b b b<br />
39 Remote setting inhibited b b b b b b b<br />
40 Remote control inhibited b b b b b b b<br />
41 Sepam not reset after fault b b b b b b b<br />
42 Remote control/position discrepancy b b b b b b b<br />
43 Matching fault<br />
or Trip Circuit Supervision<br />
b b b b b b b<br />
44 Disturbance recording memorized b b b b b b b<br />
45 Control fault b b b b b b b<br />
46 Disturbance recording inhibited b b b b b b b<br />
47 Thermal protection inhibited b b b<br />
48 RTD fault b b b<br />
Address word 0104: TS49 to TS64 (bit address 1040 to 104F)<br />
TS Use S<strong>20</strong> S23 T<strong>20</strong> T23 M<strong>20</strong> B21 B22<br />
49 Protection 38/49T alarm set point sensor 1 b b b<br />
50 Protection 38/49T tripping set point sensor 1 b b b<br />
51 Protection 38/49T alarm set point sensor 2 b b b<br />
52 Protection 38/49T tripping set point sensor 2 b b b<br />
53 Protection 38/49T alarm set point sensor 3 b b b<br />
54 Protection 38/49T tripping set point sensor 3 b b b<br />
55 Protection 38/49T alarm set point sensor 4 b b b<br />
56 Protection 38/49T tripping set point sensor 4 b b b<br />
57 Protection 38/49T alarm set point sensor 5 b b b<br />
58 Protection 38/49T tripping set point sensor 5 b b b<br />
59 Protection 38/49T alarm set point sensor 6 b b b<br />
60 Protection 38/49T tripping set point sensor 6 b b b<br />
61 Protection 38/49T alarm set point sensor 7 b b b<br />
62 Protection 38/49T tripping set point sensor 7 b b b<br />
63 Protection 38/49T alarm set point sensor 8 b b b<br />
64 Protection 38/49T tripping set point sensor 8 b b b<br />
Address check-word 0100: bit 4 (bit address 1004)<br />
Use S<strong>20</strong> S23 T<strong>20</strong> T23 M<strong>20</strong> B21 B22<br />
Bit 4 Tripping by protection function b b b b b b b<br />
5/15<br />
5