3<br />
Protection functions Setting ranges<br />
Functions Settings Time delays<br />
ANSI 27 - Phase-to-phase undervoltage<br />
5 to 100 % of Unp 0.05 s to 300 s<br />
ANSI 27D/47 - Positive sequence undervoltage<br />
15 to 60 % of Unp 0.05 s to 300 s<br />
ANSI 27R - Remanent undervoltage<br />
5 to 100 % of Unp 0.05 s to 300 s<br />
ANSI 27S - Phase-to-neutral undervoltage<br />
5 to 100 % of Vnp 0.05 s to 300 s<br />
ANSI 37 - Phase undercurrent<br />
0.15 to 1 Ib 0.05 s to 300 s<br />
ANSI 38/49T - Temperature monitoring (8 or 16 RTDs)<br />
Alarm and trip set points 0 to 180 °C (or 32 to 356 °F)<br />
ANSI 46 - Negative sequence / unbalance<br />
Definite time 0.1 to 5 Ib 0.1 s to 300 s<br />
IDMT 0.1 to 0.5 Ib 0.1 s to 1 s<br />
ANSI 48/51LR/14 - Excessive starting time, locked rotor<br />
0.5 Ib to 5 Ib ST starting time 0.5 s to 300 s<br />
LT and LTS time delays 0.05 s to 300 s<br />
ANSI 49RMS - Thermal overload Rate 1 Rate 2<br />
Accounting for negative sequence component 0 - 2,25 - 4,5 - 9<br />
Time constant Heating T1: 1 to 1<strong>20</strong> mn T1: 1 to 1<strong>20</strong> mn<br />
Cooling T2: 5 to 600 mn T2: 5 to 600 mn<br />
Alarm and tripping set points 50 to 300 % of rated thermal capacity<br />
Cold curve modification factor 0 to 100 %<br />
Switching of thermal settings conditions By logic input I26 (transformer)<br />
By Is set point adjustable from 0.25 to 8 Ib (motor)<br />
Maximum equipment temperature 60 to <strong>20</strong>0 °C (140 °F to 392 °F)<br />
ANSI 50/51 - Phase overcurrent<br />
Tripping time delay Timer hold<br />
Tripping curve Definite time DT<br />
SIT, LTI, VIT, EIT, UIT (1) DT<br />
RI DT<br />
IEC: SIT/A, LTI/B, VIT/B, EIT/C DT or IDMT<br />
IEEE: MI (D), VI (E), EI (F) DT or IDMT<br />
IAC: I, VI, EI DT or IDMT<br />
Is set point 0.1 to 24 In Definite time Inst ; 0.05 s to 300 s<br />
0.1 to 2.4 In IDMT 0.1 s to 12.5 s at 10 Is<br />
Timer hold Definite time (DT ; timer hold) Inst ; 0.05 s to 300 s<br />
IDMT (IDMT ; reset time) 0.5 s to <strong>20</strong> s<br />
ANSI 50BF - Breaker failure<br />
Presence of current 0.2 to 2 In<br />
Operating time 0.05 to 300 s<br />
(1) Tripping as of 1.2 Is.<br />