7<br />

MT10588<br />

MT10589<br />

Commissioning Checking logic input and output<br />

connections<br />

SFT2841 "Input, output, indicator status" screen.<br />

SFT2841 "Sepam Diagnosis - output relay test" screen.<br />

7/30<br />

Checking logic input connections<br />

Procedure<br />

Proceed as follows for each input:<br />

1. If the input supply voltage is present, use an electric cord to short-circuit the<br />

contact that delivers logic data to the input.<br />

2. If the input supply voltage is not present, apply a voltage supplied by the DC<br />

voltage generator to the terminal of the contact linked to the chosen input, being sure<br />

to comply with the suitable polarity and level.<br />

3. Observe the change of status of the input using the SFT2841 software, in the<br />

"Input, output, indicator status" screen.<br />

4. At the end of the test, if necessary, press the SFT2841 Reset key to clear all<br />

messages and deactivate all outputs.<br />

Checking logic output connections<br />

Procedure<br />

Check carried out using the "Output relay test" function, activated via the SFT2841<br />

software, in the "Sepam Diagnosis" screen.<br />

Only output O4, when used for the watchdog, can be tested.<br />

This function requires prior entry of the "Parameter setting" password.<br />

1. Activate each output relay using the buttons in the SFT2841 software.<br />

2. The activated output relay changes status over a period of 5 seconds.<br />

3. Observe the change of status of the output relay through the operation of the<br />

related switchgear (if it is ready to operate and is powered), or connect a voltmeter<br />

to the terminals of the output contact (the voltage cancels itself out when the contact<br />

closes).<br />

4. At the end of the test, if necessary, press the SFT2841 Reset key to clear all<br />

messages and deactivate all outputs.<br />

PCRED301005EN - 06/<strong>20</strong>08