Use SFT2841 setting and operating<br />
software<br />
Configuration of a Sepam network<br />
Configuration window for the communication network via<br />
telephone modem.<br />
PCRED301005EN - 06/<strong>20</strong>08<br />
Link via telephone modem<br />
The Sepams are connected to an RS 485 multidrop network using an industrial STN<br />
modem.<br />
This modem is the "called modem". It must first be configured, either via AT<br />
commands from a PC using HyperTerminal or the configuration tool that may have<br />
been supplied with the modem, or by setting switches<br />
(see the modem manufacturer’s <strong>manual</strong>).<br />
The PC can use an internal or an external modem. This modem on the PC side is<br />
always the calling modem. It must be installed and configured in accordance with the<br />
Windows modem installation procedure.<br />
Configuration of the calling modem in SFT2841<br />
When configuring a Sepam network, SFT2841 displays the list of all the modems<br />
installed on the PC.<br />
The communication parameters to be defined are:<br />
b modem: select one of the modems listed by SFT2841<br />
b telephone no.: no. of the remote modem to be called<br />
b speed: 4800, 9600, 19<strong>20</strong>0 or 38400 bauds<br />
b parity: none (not adjustable)<br />
b handshake: none, RTS or RTS-CTS<br />
b time-out: from 100 to 3000 ms.<br />
Communication via modem and telephone network is slowed considerably because<br />
of the transit time through the modems. A time-out of between 800 ms and 1000 ms<br />
is sufficient in most 38400 baud installations. In some cases, the poor quality of the<br />
telephone network may require a slower speed (9600 or 4800 bauds). The time-out<br />
value should then be increased (2 to 3 seconds).<br />
b number of retries: from 1 to 3.<br />
Note: The speed and parity of the calling modem must be configured in Windows with the same<br />
values as for SFT2841.<br />
7/9<br />
7