PE801<strong>20</strong><br />

Use SFT2841 setting and operating<br />

software<br />

Configuration of a Sepam network<br />

Configuration window for the communication network via<br />

telephone modem.<br />

PCRED301005EN - 06/<strong>20</strong>08<br />

Link via telephone modem<br />

The Sepams are connected to an RS 485 multidrop network using an industrial STN<br />

modem.<br />

This modem is the "called modem". It must first be configured, either via AT<br />

commands from a PC using HyperTerminal or the configuration tool that may have<br />

been supplied with the modem, or by setting switches<br />

(see the modem manufacturer’s <strong>manual</strong>).<br />

The PC can use an internal or an external modem. This modem on the PC side is<br />

always the calling modem. It must be installed and configured in accordance with the<br />

Windows modem installation procedure.<br />

Configuration of the calling modem in SFT2841<br />

When configuring a Sepam network, SFT2841 displays the list of all the modems<br />

installed on the PC.<br />

The communication parameters to be defined are:<br />

b modem: select one of the modems listed by SFT2841<br />

b telephone no.: no. of the remote modem to be called<br />

b speed: 4800, 9600, 19<strong>20</strong>0 or 38400 bauds<br />

b parity: none (not adjustable)<br />

b handshake: none, RTS or RTS-CTS<br />

b time-out: from 100 to 3000 ms.<br />

Communication via modem and telephone network is slowed considerably because<br />

of the transit time through the modems. A time-out of between 800 ms and 1000 ms<br />

is sufficient in most 38400 baud installations. In some cases, the poor quality of the<br />

telephone network may require a slower speed (9600 or 4800 bauds). The time-out<br />

value should then be increased (2 to 3 seconds).<br />

b number of retries: from 1 to 3.<br />

Note: The speed and parity of the calling modem must be configured in Windows with the same<br />

values as for SFT2841.<br />