Modbus communication Access to remote settings<br />
5/26<br />
General characteristics settings (read only)<br />
Function number: 3002<br />
Setting Data Format/Unit<br />
1 Rated frequency 0 = 50 Hz<br />
1 = 60 Hz<br />
2 Remote setting enabled 1 = disabled<br />
3 Sepam working language 0 = English<br />
1 = Customized language<br />
4 Number of period before<br />
disturbance recording<br />
1<br />
5 Active setting groupe 0 = Setting group A<br />
1 = Setting group B<br />
2 = setting group A and B<br />
3 = Choice by input I13<br />
4 = Choice by remote control<br />
5 = Logic discrimination<br />
6 Setting mode 0 = TMS<br />
1 = 10I/Is<br />
7 Type of phase current sensor 0 = 5 A CT<br />
1 = 1 A CT<br />
2 = LPTC<br />
8 Number of CTs 0 = 3 TC (I1, I2, I3)<br />
1 = 2 TC (I1, I3)<br />
9 Rated current A<br />
10 Base current A<br />
11 Residual current mode 0 = 3I sum<br />
1 = 2 A rated CSH<br />
2 = <strong>20</strong> A rated CSH<br />
3 = 1 A CT<br />
4 = 5 A CT<br />
5 = ACE990 Range 1<br />
6 = ACE990 Range 2<br />
12 Rated residual current Ino A<br />
13 Integration period 0 = 5 mn<br />
1 = 10 mn<br />
2 = 15 mn<br />
3 = 30 mn<br />
4 = 60 mn<br />
14 Reserved<br />
15 Rated primary voltage Unp V<br />
16 Rated secondary voltage Uns 0 = 100 V<br />
1 = 110 V<br />
2 = 115 V<br />
3 = 1<strong>20</strong> V<br />
4 = <strong>20</strong>0 V<br />
5 = 230 V<br />
17 Voltages mesured by VTs 0 = 3 V (V1, V2, V3)<br />
1 = 2 U (U21, U32)<br />
2 = 1 U (U21)<br />
18 Residual voltage mode 0 = none<br />
1 = 3 V sum<br />
2 = external VT – Uns/3<br />
3 = external VT – Uns/3<br />
PCRED301005EN - 06/<strong>20</strong>08