3<br />
Protection functions Breaker failure<br />
ANSI code 50BF<br />
3/24<br />
DE80107<br />
Operation<br />
This function is designed to detect when a breaker fails, i.e. when it fails to open when<br />
a trip order is sent.<br />
The "breaker failure" function is activated:<br />
b by a trip order issued by the overcurrent protection functions<br />
(50/51, 50N/51N, 46)<br />
b by an external trip order sent by logic input I24 (I24 should be assigned to external<br />
trip function 5)<br />
It checks that the current has disappeared within the time interval specified by time<br />
delay T. It can also take account of the position of the breaker read on the logic inputs<br />
to determine effective breaker opening.<br />
When the circuit breaker control function is used, the breaker failure function is<br />
activated automatically by protection units 50/51, 50N/51N and 46, which trip the<br />
breaker.<br />
When the circuit breaker control function is not used, the <strong>user</strong> has the choice of<br />
overcurrent protection functions to associate with the breaker failure protection<br />
function.<br />
The protection delayed output should be assigned to a logic output using the control<br />
matrix.<br />
Launching and stopping the time delay counter T both depend on the presence of a<br />
current above the set point (I > Is) or, according to the parameter setting, on the<br />
absence of breaker opening.<br />
Block diagram<br />
(I24) external tripping 5<br />
Note: When an external trip order is issued on input I24 of an MES114 module configured for AC,<br />
the 50BF operating characteristics are not guaranteed.<br />
PCRED301005EN - 06/<strong>20</strong>08